WIRING continued

WARNING

Electrical shock hazard.

To prevent electrical shock, death or equipment damage, disconnect power supply before 

installing or servicing this control.

ZONE VALVE WIRING

IMPORTANT: 

Use a separate transformer to power zone valves. Connecting zone valves to Z-TV may overload the

HydroStat and cause a lock-out condition (see 

Troubleshooting

on page 12 for more information). The total load, including

the burner circuit, vent damper, and Z-TV connections must not exceed 1.2 amps (30 VA). Connect zone valve end-switch
to T/TV as shown below.

STEP 6  For Systems with Indirect Water Heaters

When installing with an indirect water heater, the signal from the indirect must be separated from the heating zone signals and
wired to 

I1

and 

I2

as shown above. Calls to I1 and I2 will bypass the Thermal Targeting or Outdoor Reset feature and allow the

boiler to fire to the high limit setting to heat the indirect tank. 

NOTE:

If you choose not to separate the indirect signal from the heating zones, the Economy Feature should be turned OFF to

insure that the boiler supplies adequate temperature to heat the indirect tank (see page 4).

Содержание FUEL SMART HydroStat 3200-Plus

Страница 1: ...Hydrolevel OS 100 Outdoor Sensor Kit sold separately for out door reset and warm weather shut down functionality INSTALLATION INSTRUCTIONS and OPERATING MANUAL Saves Fuel Features Thermal Targeting te...

Страница 2: ...circuit to B1 B2 B2 is common STEP 4 Connect the thermostat to T TV STEP 5 If the boiler is equipped with a plug in style vent damper unplug the factory installed jumper from the recepta cle on the ci...

Страница 3: ...s must not exceed 1 2 amps 30 VA Connect zone valve end switch to T TV as shown below STEP 6 For Systems with Indirect Water Heaters When installing with an indirect water heater the signal from the i...

Страница 4: ...zone house turn the dial to 2 or 1 Conversely if the boiler provides adequate heat added fuel savings can be achieved by selecting a higher setting example 4 or 5 If the heating and indirect water hea...

Страница 5: ...time to satisfy the heat load NOTE Smart DHW Priority During a call from an indirect water heater the control will de energize the circulator contacts C1 C2 to heat only the indirect tank ensuring an...

Страница 6: ...Turn the HI TEMP dial to select feature 2 3 Push the Test Settings Button to c for Celsius or F for Fahrenheit 4 Reset LO TEMP and HI TEMP settings to desired temperatures see page 4 Manual Reset Low...

Страница 7: ...desired temperatures see page 4 Setting the Well Type Electro Well vs Standard Immersion Well When used to replace older temperature only controls the HydroStat can be installed on the existing well...

Страница 8: ...n the display as Pro 2 Turn the HI TEMP dial to select feature dEf 3 Push the Test Settings Button toY to reset all features to the default settings 4 Reset LO TEMP and HI TEMP settings to desired tem...

Страница 9: ...e the LED illuminates and the burner will shut down The boiler water will continue to circulate and heat the house as long as the thermostat call continues The LED will stay lit until the boiler tempe...

Страница 10: ...with the inside of the well tube Check that the well does not have excessive build up of heat transfer grease that may interfere with the clip contacting the well 2 Remove well and examine for excessi...

Страница 11: ...erve fuel see How Thermal Targeting Works on page 5 The burner will not fire until the boiler temperature drops to the automatically calculated Target Temp Differential YES NO Is the Green LED TEMP AC...

Страница 12: ...should never fire when red or yellow LED is lit Is either Yellow LED On The Control has Reached Target or High Limit Temperature The Control is Operating Normally The Control is Operating Normally Th...

Отзывы: