INSTRUCTIONS

13

NOTE: Please note that the filter (with the pump) must be located below the reservoir water level. 

If you wish to place the unit at the side of the reservoir, you must fill the filtration system with 

water before turning it on.

OPERATION

1.  Do NOT power on the chiller unit yet. Fully submerge the water pump to be used, plug it in, and ensure 

that water is moving freely between the holding reservoir and the chiller unit.

2.  Plug the chiller into a grounded outlet and ensure the power switch located on the back of the 

unit is in the “ON” (I) position.

WARNINGS:

•  Do NOT cover the chiller unit with anything during operation.
•  Place the chiller in the upright position ONLY for operation and storage purposes.
•  Avoid direct contact with liquids to the external body of the chiller unit. Failure to do so may 

result in damage to the unit or electric shock.

•  Keep power cord free of obstructions, such as heavy or sharp objects sitting directly on it.
•  This chiller is approved for indoor use ONLY.
•  Keep the unit away from flammable vapors, direct sunlight, high temperature exposure, and high 

humidity.

•  Do NOT submerse the chiller. Doing so will damage the unit and may inflict electric shock.

SETTING THE TEMPERATURE:

1.  Press and hold the SET button down for approximately 3 seconds to enter the water temperature 

programming mode. The previous water temperature setting will display.

2.  Use the /\ or \/ buttons on the control panel to increase or decrease the desired water 

temperature. Press the SET button once more, or wait approximately 8 seconds to select the 

desired temperature.

TEMPERATURE DISPLAY:

Press the SET button once to display the current set temperature value of the chiller unit, then 

press the SET button again to display the actual temperature value of the water. The blinking display 

indicates the set temperature.

TEMPERATURE ERROR ADJUSTMENT:

1.  When the reservoir water temperature differs from the set temperature value, a “II” indication 

should appear in the display.

2.  Press and hold the /\ and \/ buttons at the same time for approximately 6 seconds to enter the error 

adjustment programming mode. The display will blink once this status is active.

3.  By pressing either the /\ or \/ buttons, the error adjustment range can be mo/- 1.5 degrees 

Celsius. DO NOT USE THIS FUNCTION UNLESS IT IS NECESSARY.

Содержание ActiveAqua AACH100HP

Страница 1: ...INSTRUCTIONS WATER CHILLERS AACH10HP AACH25HP AACH50HP AACH100HP ...

Страница 2: ...INSTRUCTIONS www Hydrofarm com 2 AACH10HP CHILLER 1 10 HP 10 40 GALLON ...

Страница 3: ...er filter and the circulation equipment 2 The refrigeration performance test is indicated when the ambient temperature is 100 F 34 C the reservior capacity is 10 gal to 40 gal the chilling efficiency reaches its best 3 The refrigeration efficiency is determined according to the installation location heating source lighting pump filter and other connecting parts 4 When there is not enough circulati...

Страница 4: ...INSTRUCTIONS www Hydrofarm com 4 AACH25HP CHILLER 1 4 HP 26 80 GALLON ...

Страница 5: ... circulation equipment 2 The refrigeration performance test is indicated when the ambient temperature is 100 F 34 C the reservior capacity is 40 gal to 90 gal the chilling efficiency reaches its best 3 The refrigeration efficiency is determined according to the installation location heating source lighting pump filter and other connecting parts 4 When there is not enough circulation in a room the ...

Страница 6: ...INSTRUCTIONS www Hydrofarm com 6 AACH50HP CHILLER 1 2 HP 52 132 GALLON ...

Страница 7: ...circulation equipment 2 The refrigeration performance test is indicated when the ambient temperature is 100 F 34 C the reservior capacity is 90 gal to 172 gal the chilling effciency reaches its best 3 The refrigeration efficiency is determined according to the installation location heating source lighting pump filter and other connecting parts 4 When there is not enough circulation in a room the r...

Страница 8: ...INSTRUCTIONS www Hydrofarm com 8 AACH100HP CHILLER 1 HP 80 250 GALLON ...

Страница 9: ...filter and the circulation equipment 2 The refrigeration performance test is indicated when the ambient temperature is 100 F 34 C the reservior capacity is 132 gal to 396 gal the chilling effciency reaches its best 3 The refrigeration efficiency is determined according to the installation location heating source lighting pump filter and other connecting parts 4 When there is not enough circulation...

Страница 10: ...can OAK production line Anti corrosive pure titanium evaporator for fresh and salt water The compressor protection device system is built to shut off the circuit automatically to prevent the motor from burning out when it is overheating Temperature memory system that allows the chiller to refrigerate continuously according to the previous temperature setting Boost function accelerates the chilling...

Страница 11: ... personal injuries or damage to the chiller Please familiarize yourself with the symbols below before reading the manual or trying to operate the chiller TERMS AND SYMBOLS Hazard levels will be indicated in writing or shown by pictures The symbol on the left provides general emphasis of the hazard but specific details of the action which must be taken will be shown by a picture or explanation near...

Страница 12: ...MBLY INSTRUCTIONS 1 Remove the chiller unit and all of the contained hardware from the box and packaging material 2 Set the chiller unit upright in the desired area on a stable surface ensuring there is at least 1 of clearance around the body sides top and back of the unit 3 Install the inlet outlet fittings onto the inflow and outflow threaded sites NOTE If the inflow and outflow fittings are dif...

Страница 13: ...ight high temperature exposure and high humidity Do NOT submerse the chiller Doing so will damage the unit and may inflict electric shock SETTING THE TEMPERATURE 1 Press and hold the SET button down for approximately 3 seconds to enter the water temperature programming mode The previous water temperature setting will display 2 Use the or buttons on the control panel to increase or decrease the des...

Страница 14: ...ear when the compressor is active The indicator light will disappear when the set water temperature has been reached and will blink when the compressor is in the 3 minute protection mode ERROR CODE Certain text will appear on the display panel in the event of an error P1 is an example that means there is a defect in the temperature sensor If error codes are appearing on the display return the unit...

Страница 15: ...UM OR RINSE TROUBLESHOOTING SYMPTOM CAUSE SOLUTION The unit doesn t run and the display is blank Power is not turned on Turn on the power Plugged in incorrectly Be sure the power cord is fully plugged in The unit cycles on and off Wrong voltage and or frequency Apply to correct power source Chiller is in protection mode A Check if the water circulation is normal B If the fan and the chiller dissip...

Страница 16: ... ou autres en rapport avec le produit Certains états n autorisent aucune limite concernant la durée de la garantie implicite ou l exclusion des dommages fortuits ou consécutifs les limites ou exclusions mentionnées ci dessus peuvent donc ne pas être applicables à votre cas Hydrofarm se réserve le droit de réparer ou remplacer le chiller couvert par cette garantie si celui ci est renvoyé au lieu d ...

Отзывы: