1.   General

1.1  It is important these Installation and Maintenance Instructions are fully  
 

adhered to.

1.2  Full details of the unit supplied are shown on the product nameplate. If in  
 

doubt about any detail contact Hydor or its agents for clarification.

1.3  All electrical installation must be carried out by suitably qualified and  
 

competent personnel in accordance with all current statutory  

 requirements.
1.4  These instructions cover only the Hydor product and do not include  
 

the supply or installation of any safety equipment that may be required  

 

e.g. adequate guarding or protection from rotating parts and proper  

 

electrical isolation.

1.5  Any declarations made by Hydor about product installation and safety,  
 

are dependent on the fan equipment being used within installations which  

 

themselves meet the requirements of the relevant Standards and    

 

Directives of your region.

1.6  The fan is designed for use in an ambient temperature of -20°C up to a  
 

maximum of +70°C, speed controlled operating

 

temperatures of -20°C and +50°C and up to 95% relative humidity. EC fans  

 

are designed for ambient temperatures up to +60°C. The fan is not   

 

suitable for corrosive or explosive atmospheres.

1.7  The installer should provide easy access to the fan to facilitate future  
 maintenance.
1.8  The installer should ensure the fan is adequately supported.
1.9  This product is not intended for use by persons (including children) with  
 

reduced physical, sensory or mental capabilities, or lack of experience and  

 

knowledge, unless they have been given supervision or instruction  

 

concerning use of the product by a person responsible for their safety.  

 

Children should be supervised to ensure that they do not play with 

 

the product.

1.10  At end-of-life, the unit must be disposed of in an environmentally friendly  
 

manner by suitably qualified and competent personnel in accordance with  

 

the requirements of applicable Standards and Directives.

2.   Installation

 WARNING: 

The fan must be isolated from the power supply during  

 

installation and maintenance. The fan must be earthed in accordance  

 

with the local regulations.

2.1  Upon receipt, the fan equipment should be visually inspected to check for  
 

any damage. Ensure that the impeller is free to rotate.

2.2  If there are any queries concerning the fan equipment, Hydor should be  
 

contacted prior to the installation.

2.3  The fan must be securely mounted in the desired position to suit the  

Содержание HXP EC

Страница 1: ...wners Installation and Maintenance Instructions THESE INSTRUCTIONS MUST BE READ FULLY BEFORE COMMENCING INSTALLATION Owner installer The life of this apparatus and its efficiency will be increased if its use and maintenance is carried out in accordance with these instructions and current statutory requirements The installation and initial adjustments should be carried out by a qualified and compet...

Страница 2: ...es up to 60 C The fan is not suitable for corrosive or explosive atmospheres 1 7 The installer should provide easy access to the fan to facilitate future maintenance 1 8 The installer should ensure the fan is adequately supported 1 9 This product is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless the...

Страница 3: ...erval between consecutive starts 5 minutes 3 5 Maximum 1 connection from power supply cycle per 5 minutes 4 Fan Maintenance 4 1 Inspection of the fan at least once every 3 months is recommended to ensure that the motor fan blades and supporting guards are clean Any build up of dust and deposits on the blades or guards should be removed using a non abrasive cleaner 4 2 All fastenings including elec...

Страница 4: ... to the external control is limited by the potentiometer setting of the commissioning device 10 07 2018 MK 149 CD POT Issue Saved Date A The 149 CD POT is a commissiong device designed to be used with our EC range of fans The device will allow the for the installer to set the maximum operating speed of the fan that it is connected to The installer or commissioning engineer can adjust the fan speed...

Страница 5: ... fan controller compatibility GND 10V E1 MIN MAX E1 GND ST1 ST2 GN MAX MIN ST1 GN THE A ST2 C YOU C DISCO MULT BETW PLEAS THIS IS THE INTERNAL POTENTIOMETER THIS POTENTIOMETER CAN BE ADJUSTED FOR SINGLE SPEED SETTING OR MAX SPEED SELECTION THIS LINK JUMPER SHOULD BE REMOVED WHEN USING AN EXTERNAL POTENTIOMETER OR EXTERNAL CONTROL SIGNAL CONNECTED TO ST1 TH S C 149 CD POT 10 07 2018 POT Issue Saved...

Страница 6: ...60 1EC SCP630 1EC SCP710 1EC 1 4 3 2 149 CD POT ST2 ST1 GND E1 MAX MIN E1 10V GND GREEN YELLOW BROWN BLUE 1PH EC SINGLE FAN C W ONEWAY SWITCH SINGLE FAN N L 220 277V1PH50Hz MAINS SUPPLY BROWN BLUE G Y YELLOW WHITE BLUE RED CONTROLS POWER L N PE MAX SPEED TRIMMER JUMPER REMOVED BROWN BLACK 5 6 FOR USEWITH SCP250 1EC SCP315 1EC SCP350 1EC SCP400 1EC SCP450 1EC SCP500 1EC SCP560 1EC SCP630 1EC SCP710...

Страница 7: ... NGLE FAN AL Tag Purpose Description L Live Live power supply 220 277V N Neutral Neutral from power supply Permanent Earth Permanent earth from power supply 1 DCVoltage 2 10V DC control voltage input 2 to 10VDC input 2 DC Current 4 20mA DC control current input 4 to 20mA input 3 Frequency 10 95 Frequency duty cycle PWM Voltage 10 to 24Vpk Frequency 80Hz 10 to 95 input 4 Speed Reference Tacho outpu...

Страница 8: ...eturns Note Number carriage paid for further examination EG Agri Ltd Hydor Unit 8 Parkers Close Downton Business Centre Downton Salisbury Wiltshire SP5 3RB UK Tel 44 0 1725 511422 Email info hydor co uk Web www hydor co uk idealair group Unit 1 Building 1 Sydney Corporate Park 85 O Riordan Street Alexandria NSW 2015 Tel 61 02 8073 3310 Fax 61 02 8073 3320 Email info idealairgroup com au AMS 11 Ing...

Отзывы: