
14
HNS
526
Version: 06.10.2014
HYDAC
ELECTRONIC
GMBH
Part No.: 669869
E
7.2 Setting ranges of the switch points or switch back points
Operational
scanning
range
SP1, SP2, FH1,
FH2 *
RP1, RP2, FL1,
FL2*
280 mm
2 .. 32 cm
2 .. 13 inch
1 .. 31 cm
1 .. 12 inch
480 mm
2 .. 59 cm
2 .. 23 inch
1 .. 58 cm
1 .. 22 inch
1600 mm
2 .. 180 cm
2 .. 71 inch
1 .. 179 cm
1 .. 70 inch
4000 mm
2 .. 465 cm
2 .. 183 inch
1 .. 464 cm
1 .. 182 inch
6400 mm
2 .. 740 cm
2 .. 291 inch
1 .. 739 cm
1 .. 290 inch
* The increment for all units is 1 cm or 1 inch.
The maximum setting ranges are given. The setting of the "bot" and "top" parameters
determines how the setting ranges are reduced.
* 1 unit
= 1 cm or. 1 inch, when setting the maximum measuring range (bot – top)
= 1 cm, 1 inch or, otherwise, 1 %
Minimum level
0
bot
SP
SP (FH)
max
= N
max
N
max
Maximum level
RP (FL)
RP (FL)
max
= N
max
– 1 unit*
SP
SP (FH)
min
= 2 units *
RP (FL)
RP (FL)
min
= 1 unit *
top
Blind
Maximum scanning
range
0
bot – top
> 3 units* *
Содержание HNS 526
Страница 28: ...28 HNS 526 Stand 06 10 2014 HYDAC ELECTRONIC GMBH Mat Nr 669869 D Betriebstastweite 6400 mm ...
Страница 60: ...28 HNS 526 Version 06 10 2014 HYDAC ELECTRONIC GMBH Part No 669869 E Operational scanning range 6400 mm ...
Страница 92: ...28 HNS 526 Edition 06 10 2014 HYDAC ELECTRONIC GMBH Code art 669869 F Plage de fonctionnement 6400 mm ...