HWg-PWR 3 / 12 / 25 MANUAL
HW group
September 2013
page 30
Edit xMeter section
Enable
– Enables or disables the meter within HWg-PWR. When a meter is disabled,
values are not detected or read but the configured parameters remain stored. This can
be used to temporarily turn off the reading and recording for a particular meter
(during maintenance etc.)
The
Use Address
option configures the addressing mode (
Primary
– shorter primary M-
Bus address;
Secondary
– unique secondary address). For battery-powered meters, we
recommend to use the primary address.
PRI Address
– Primary address on the M-Bus. The address is entered as one byte (0-
255). Meters of the same type and by the same manufacturer are often supplied with
the same Primary address, which therefore cannot be used for addressing. The field
allows changing the primary address as a convenience for battery-powered meters.
Secondary Address
– Secondary address on the M-Bus. This address is used to identify
a meter if there are more meters with the same primary address (
Address
field) on the
bus. Secondary address is not user-changeable.
Serial Baudrate
– M-Bus communication speed for the particular meter. By default,
2400 Baud is configured. Meters with different communication speeds can coexist on
a single bus; this parameter sets the speed for the particular meter.
Serial Parity
– M-Bus communication parity. As with the baudrate, parity can be
specified individually for each meter.
Meter M-Bus Read period
sets the interval for reading out the values from the meter.
The default is 30s. For battery-powered meters, it might be advisable to set a longer
period. For details, see
Meter types
.
Name
– Meter name. Identifies the meter within HWg-PWR – in graphs, XML and
SNMP – using a custom name (Home, Office, RACK1, etc.).
Scan Value
– Reads the values and their parameters from the meter. See
First Steps
.