background image

11

branch top that close to fault region, or connect to DC bus bar at the bottom of
loop. When detecting, signal generator should be always connected to power
supply terminal of DC branch, and the fault detector and the signal receiver are
always testing at the load end of DC branch.

3. Signal receiver

Fig.2 Panel layout for signal receiver

Port for A clamp: Connect "A" clamp, the clamp is big clamp.
Port for B pliers: Connect "B" pliers, this clamp is a small pliers.
LCD: dot matrix LCD display.
Power switch: Press "ON / OFF" key to start up/shut down.

Instructions for Signal receiver:

With calipers respectively clamp all main circuit that were associated with

fault bus bar, and then observe LCD display. Use number 0-19 from low to
high to indicate insulation value, “01” indicating poor insulation, “19” indicating
good insulation. When LCD displays a lower value, you can judge fault is on
this main circuit, and then with calipers measure branch circuit that linked to
faulted main circuit, through LCD display value you can determine broken
branch, and so on, using the same method can find the final faulted branch.

Found the earthed branch, for the fault point you can do location detection.

When testing, user can use dichotomy to detect faulted area. In each test, the

Port for A clamp

Port for B pliers

LCD

Power switch

Содержание PDF1000

Страница 1: ...You can find the changes in the appendix Sorry for the inconvenience If you have further questions welcome to contact with our service department The input output terminals and the test column may br...

Страница 2: ...refully to avoid body injury and prevent the product or other relevant subassembly to damage In order to avoid possible danger this product can only be used within the prescribed scope Only qualified...

Страница 3: ...t Before connecting please read the instruction manual to acquire information about the ratings Do Not Operate without Covers Do not operate this product when covers or panels removed Use Proper Fuse...

Страница 4: ...Security Terms Warning indicates that death or severe personal injury may result if proper precautions are not taken Caution indicates that property damage may result if proper precautions are not tak...

Страница 5: ...5 Contents I Overview 6 II Principle 7 III Specifications 8 IV Structure and Function of Instrument 9 V Notes 12 Appendix 1 structural representation 14 Appendix 2 brief method introduction 15...

Страница 6: ...system The DC system of power plant and transformer substation is the power supply for control protect signal and auto equipment the safe continuous running is very important to generate and supply p...

Страница 7: ...ction under no power interruption no effect to system normal work strong anti jamming ability safe and reliable Waveform analysis inject one special cyclical voltage signal between DC bus bar and grou...

Страница 8: ...t circuit output current 80mA Output terminal shock resistance capability 400V DC impulse Supply voltage AC220V 10 Voltage frequency 50Hz 5 Single chip Signal sampling analog to digital conversion Sig...

Страница 9: ...2 5mA Display of receiver number 0 19 Dimension 210x100x32mm A jaw size 50mm B jaw size 7mm 9mm 3 Complete appliance Measured maximum ground resistance 300k Ground resistance measurement accuracy 0 4...

Страница 10: ...cating having normal low frequency voltage output Signal output the port for signal output When using please insert output leads to output signal Access signal generator Insert signal output leads int...

Страница 11: ...s for Signal receiver With calipers respectively clamp all main circuit that were associated with fault bus bar and then observe LCD display Use number 0 19 from low to high to indicate insulation val...

Страница 12: ...at let the calipers firmly clamp the feeder cables until obtain stable measured data 4 Signal output lead Red lead connects to fault bus bar terminal black lead connects to ground Red plug inserts int...

Страница 13: ...ow battery please replace the battery timely to improve measurement accuracy 7 Since the receiver has high sensitivity when testing please do not grasp it let the receiver in quiescent state so as not...

Страница 14: ...14 Appendix 1 structural representation...

Страница 15: ...generator 3 Insert the plug of the caliper with the input jack of the signal receiver 4 Turn on the power switch of the signal receiver 5 Strangulate the measured circuit using caliper 6 Begin to test...

Страница 16: ...16...

Отзывы: