background image

www.h-v-c.com

Operation and maintenance manual

NCA Series 400H hand operated single blade leakage rated fire damper

Regular inspection and maintenance of fire dampers is essential to 
ensure they remain in good working condition. It is the system owner’s 
responsibility to ensure this is carried out. 

In accordance with EN 15650:2010 fire damper maintenance routines, 
such as that given below, must be carried out at intervals not exceeding 6 
months. 

Some automatic systems may allow more frequent testing (48 hours or 
less) and this may be required by national regulation. 

Please note: 

This document is relevant only to hand operated S400 

 

dampers. For S400 dampers equipped with an actuator 

 

please see the relevant document. 

Installation guide: NCA Series 400 hand operated single blade leakage rated fire damper

Operation and maintenance manual
Page 1 of 3 - Issue A - 03/03/2022

Damper type:

NCA Series 400H hand operated single blade leakage rated fire damper

Thermal link rated temperature:

Delete as appropriate

68°C (red bulb in link) or 93°C (green bulb in link)

Damper reference (if applicable):

Damper location (within site):

Date of inspection:

Step Operation

Notes

Yes/No

1

Is the damper open?

The damper handle should be parallel with the damper body, indicating the 
damper is open 

2

Is the handle mechanism secure and 
undamaged?

Using a pozi-drive screwdriver, ensure the machine screw inside the spindle 
cap is secure

3

Remove access door/s to access the inside of 
ductwork and damper blade

Both sides of the damper blade should be easily accessible

N/A

4

Is the damper blade in the fully open position 
and secure?

The damper blade should be in the fully open position. 
Gently try to move the blade by hand, it should not rotate.

5

Is the damper blade unobstructed?

Ensure there is nothing present which is obstructing or could obstruct the 
damper blade operating

6

Is the thermal link clean and free from 
damage and corrosion?

Thermal links must be cleaned with care and if damaged or heavily soiled 
must be replaced
Caution - Thermal links are fragile

7

Is the damper blade and case clean and free 
from damage and corrosion?

Use a damp cloth, brush or vacuum cleaner to remove any dirt and debris. 
If damaged or corroded dampers must be replaced
Caution - Blade sealing fabric is sharp, PPE should be used

8

Does the damper close correctly?

Pull the test handle on the external mechanism, the damper should close

9

Does the damper open correctly?

Rotate the setting handle 90° anti-clockwise until the underside of the handle 
latches onto the thermal link

10

Do you have any concerns about the 
installation?

Is there anything that does not look correct, do you have any doubts etc.?

11

Refit access door/s securely

N/A

N/A

Periodic maintenance procedure

If any of questions 1 - 9 is answered ‘no’, or if the answer to 
question 10 is ‘yes’, please see troubleshooting overleaf. 

Отзывы:

Похожие инструкции для NCA Series