17
16
FC = Limit switch - end
C = common
NF = normally closed
DC = Limit switch - start
NO = normally open
ELECTRICAL SPECIFICATIONS
FD25 FUSE ONLY
FD25/FD40 FUSE ONLY UPGRADABLE TO SOLENOID
ACTUATOR
Nominal voltage
N/A
Solenoid: 24/48 VDC
(automatic change on the electronic card)
Power
N/A
Dual voltage SOLENOID:
• Break of current: Pnom = 1.6W
• Emission of current: Pmax = 3.5 W
Switching capacity of the FDCU
and FDCB contactors
1mA…500mA,
5VDC…48VDC
1mA…500mA, 5VDC…48VDC
Blade closure time
Blade opening time
Spring: 1 second
Manual
Spring: 1 second
Degree of protection
IP 42
IP 42
8. OTHER MECHANISMS
Belimo
Operation
Damper is delivered in closed position. When
electric actuator is connected to the power
supply damper will open. When the damper
reaches the end position (damper open), in
which is it blocked, the electromotor will stop.
Closing fire damper takes place automati¬cally
when a power failure occurs. Thermal tripping
device that comes with fire damper causes
power circuit break at a temperature of 72 °C
(inside or outside duct). If checking is needed
for proper functioning of fire damper, pushing
the switch on the thermal tripping device will
close damper. When switch on tripping device
is released, the damper will open.
Damper can be opened without connecting
to a voltage with enclosed handle turning in
the direction of the arrow on electric actua
-
tor (clockwise). Damper can be locked in the
desired position by fast turning back handle
a quarter of a turn (counterclockwise) for Be-
limo BF, and by puling brake on Belimo BFL
and BFN.
To unlock the electromotor, turn handle clock
-
wise for a quarter of a turn for Belimo BF, or
release brake for Belimo BFL and BFN. After re
-
lease, damper will be closed by return spring.
When damper is opened manually, electric
actuator will not move the damper into closed
position after power failure (ther¬moelectric
fuse).
Type of Belimo actuator
BFL24-T
BFN24-T
BFL230-T
BFN230-T
BF24-T
BF230-T
Nominal
voltage /
power con-
sumption
voltage
AC/DC 24V,
50/60Hz
AC 24V,
50/60Hz
AC 230V,
50/60Hz
AC 230V,
50/60Hz
AC/DC 24V,
50/60Hz
AC 230V,
50/60Hz
opening
2,5 W
4 W
3,5 W
5 W
7 W
8.5 W
holding
0,8 W
1,4 W
1,1 W
2,1 W
2 W
3 W
for wire sizing
4 VA
6 VA
6,5 VA
10 VA
10 VA
11 VA
End switch
1 mA...3 A
(0,5 A), DC 5
V...AC 250V
1 mA...3 A
(0.5 A), DC 5
V...AC 250 V
1 mA...3 A
(0.5 A), DC 5
V...AC 250 V
1 mA...3 A
(0.5 A), DC 5
V...AC 250 V
1 mA...6 A (3
A), DC 5 V...
AC 250 V
1 mA...3 A
(0.5 A), DC 5
V...AC 250 V
Running
time
motor
<60 s
<60 s
<60 s
<60 s
<120 s
<120 s
spring-return
~20 s
~20 s
~20 s
~20 s
~16 s
~16 s
Ambient temperature range
min. -30°C, max. 50°C
Wiring diagram
Содержание Klimaoprema FDC25