HVAC Partners R2A3 Скачать руководство пользователя страница 7

INSTALLATION INSTRUCTIONS

R

22 Split System Air Conditioner

421 01 5203 02

7

Specifications subject to change without notice.

After the refrigerant charge has bled into the system,

open the Liquid service valve.

NOTE:

 These are not back

seating valves. It is not

necessary to force the stem tightly against the rolled lip.
The service valve cap is a primary seal for the valve and

must be properly tightened to prevent leaks. Make sure

cap is clean and apply refrigerant oil to threads and

sealing surface on inside of cap.
Tighten cap finger tight and then tighten additional 

6

 of a

turn (1 wrench flat) to properly seat the sealing surfaces.

J. GAUGE PORTS

Check for leaks at the schrader ports and tighten valve

cores if necessary. Install plastic caps finger tight.

ELECTRICAL WIRING

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in

personal injury or death.
Before installing, modifying or servicing system,

main electrical disconnect switch must be in the

OFF position. There may be more than 1

disconnect switch. Lock out and tag switch with a

suitable  warning label.

The supply voltage must be 208/230 volts (197 volt

minimum to 253 volts maximum) 60 Hz single phase.
Outdoor units are approved for use with copper

conductors only. Do not use aluminum wire.

Refer to unit rating plate for minimum circuit ampacity and

circuit protection requirements.

Grounding

Permanently ground unit in accordance with the National

Electrical Code and local codes or ordinances. Use a

copper conductor of the correct size from the grounding

lug in control box to a grounded connection in the service

panel or a properly driven and electrically grounded

ground rod.

Wiring Connections

Make all outdoor electrical supply (Line Voltage)

connections with raintight conduit and fittings. Most

codes require a disconnect switch outdoors within sight of

the unit. Consult local codes for special requirements.
Route electrical supply (Line Voltage) wiring through

knockout hole in bottom of Control Box. Connect wires to

Contactor and Ground Lug according to Wiring Diagram

on unit. Also refer to Figure 9.
Route thermostat wiring through rubber grommet in

bottom of Control Box. Low voltage lead wires are

provided in the control box for connection to thermostat

wires (use wire nuts). Refer to Wiring Diagram on unit and

Figure 10 for low voltage wiring examples.

NOTE:

 Use No. 18 AWG (American Wire Gage)

color

coded, insulated (35 

°

C minimum) wire. If

thermostat is located more than 100 feet (31m) from unit

as measured along the control voltage wires, use No. 16

AWG color

coded wires to avoid excessive voltage drop.

Figure 9

Electrical Supply (Line Voltage) Connections

DISCONNECT

PER NEC AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

11

23 or 13

L1

L2

Содержание R2A3

Страница 1: ...used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combinatio...

Страница 2: ...to CLEARANCES section of this document Roof top installation is acceptable providing the roof will support the unit and provisions are made for water drainage and noise vibration dampening NOTE Roof...

Страница 3: ...HES Check to see that the proper system components are in place especially the indoor coil R 22 outdoor units can only be used with R 22 specific indoor coils If there is a refrigerant mis match consu...

Страница 4: ...refrigerant to the atmosphere Recover during system repair or final unit disposal C ROUTING AND SUSPENDING REFRIGERANT LINES Run refrigerant lines as straight and direct as possible avoiding unnecessa...

Страница 5: ...EFORE brazing This helps prevent overheating and damage to valve seals refer to Figure 6 Replace valve core when brazing is completed Figure 6 Service Valve VALVE CORE SERVICE VALVE WARNING FIRE HAZAR...

Страница 6: ...uum Gauge Response and System Conditions 500 MINUTES 0 1 2 4 6 1000 1500 LEAK IN SYSTEM VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 2000 MICRONS 2500 3000 3500 4000 4500 5000 3 7 5 Triple Evacuation Method...

Страница 7: ...r to unit rating plate for minimum circuit ampacity and circuit protection requirements Grounding Permanently ground unit in accordance with the National Electrical Code and local codes or ordinances...

Страница 8: ...l charge 3m x 17g 51g additional charge This outdoor unit is designed for use only with indoor coils that utilize a TXV refrigerant metering device With an indoor TXV use the subcooling method to make...

Страница 9: ...wer motor When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipped with a time delay relay circuit the blower...

Отзывы: