INSTALLATION INSTRUCTIONS

R

22 Split System Air Conditioner

6

421 01 5203 02

Specifications subject to change without notice.

H. EVACUATING LINE SET AND INDOOR COIL

The unit is shipped with a factory refrigerant charge. The

liquid line and suction line service valves have been

closed after final testing at the factory. Do not disturb

these valves until the line set and indoor coil have been

evacuated and leak checked, or the charge in the unit

may be lost.

NOTE:

 Do not use any portion of the factory charge for

purging or leak testing. The factory charge is for filling the

system only after a complete evacuation and leak check

has been performed.

!

CAUTION

PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product

damage.
Never use the outdoor unit compressor as a

vacuum pump. Doing so may damage the

compressor.

Line set and indoor coil should be evacuated using the

recommended deep vacuum method of 500 microns. If

deep vacuum equipment is not available, the alternate

triple evacuation method may be used by following the

specified procedure.
If vacuum must be interrupted during the evacuation

procedure, always break vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump

capable of pulling a vacuum to 500 microns and a vacuum

gauge capable of accurately measuring this vacuum

level. The deep vacuum method is the most positive way

of assuring a system is free of air and water.
Watch the vacuum gauge as the system is pulling down.

The response of the gauge is an indicator of the condition

of the system (refer to Figure 7).
With no leaks in the system, allow the vacuum pump to

run for 30 minutes minimum at the deep vacuum level.

Figure 7

Deep Vacuum Gauge Response

and System Conditions

500

MINUTES

0

1

2

4

6

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET

TIGHT

DRY SYSTEM

2000

M

ICRONS

2500

3000

3500

4000

4500

5000

3

7

5

Triple Evacuation Method

The triple evacuation method should only be used when

system does not contain any water in liquid form and

vacuum pump is only capable of pulling down to 28 inches

of mercury (711mm Hg). Refer to Fig. 8 and proceed is as

follows:

1. Pull system down to 28 inches of mercury (711mm

Hg) and allow pump to continue operating for an

additional 15 minutes.

2. Close manifold valves or valve at vacuum pump

and shut off vacuum pump.

3. Connect a nitrogen cylinder and regulator to

system and fill with nitrogen until system pressure

is 2 psig.

4. Close nitrogen valve and allow system to stand for

1 hour. During this time, dry nitrogen will diffuse

throughout the system absorbing moisture.

5. Repeat this procedure as indicated in Figure 8.
6. After the final evacuate sequence, confirm there

are no leaks in the system. If a leak is found, repeat

the entire process after repair is made.

Figure 8

Triple Evacuation Sequence

CHECK FOR TIGHT, DRY SYSTEM

(IF IT HOLDS DEEP VACUUM)

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHARGE SYSTEM

BREAK VACUUM WITH DRY NITROGEN

EVACUATE

WAIT

I. OPENING SERVICE VALVES

Outdoor units are shipped with a refrigerant charge

sealed in the unit. Opening the service valves releases

this charge into the system.

NOTE:

 Open the Suction service valve first. If the Liquid

service valve is opened first, oil from the compressor may

be drawn into the indoor coil TXV, restricting refrigerant

flow and affecting operation of the system.
Remove Suction service valve cap and insert a hex

wrench into the valve stem. Hold the valve body steady

with an end

wrench and back out the stem by turning the

hex wrench counterclockwise. Turn the stem until it just

contacts the rolled lip of the valve body.

Содержание R2A3

Страница 1: ...used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combinatio...

Страница 2: ...to CLEARANCES section of this document Roof top installation is acceptable providing the roof will support the unit and provisions are made for water drainage and noise vibration dampening NOTE Roof...

Страница 3: ...HES Check to see that the proper system components are in place especially the indoor coil R 22 outdoor units can only be used with R 22 specific indoor coils If there is a refrigerant mis match consu...

Страница 4: ...refrigerant to the atmosphere Recover during system repair or final unit disposal C ROUTING AND SUSPENDING REFRIGERANT LINES Run refrigerant lines as straight and direct as possible avoiding unnecessa...

Страница 5: ...EFORE brazing This helps prevent overheating and damage to valve seals refer to Figure 6 Replace valve core when brazing is completed Figure 6 Service Valve VALVE CORE SERVICE VALVE WARNING FIRE HAZAR...

Страница 6: ...uum Gauge Response and System Conditions 500 MINUTES 0 1 2 4 6 1000 1500 LEAK IN SYSTEM VACUUM TIGHT TOO WET TIGHT DRY SYSTEM 2000 MICRONS 2500 3000 3500 4000 4500 5000 3 7 5 Triple Evacuation Method...

Страница 7: ...r to unit rating plate for minimum circuit ampacity and circuit protection requirements Grounding Permanently ground unit in accordance with the National Electrical Code and local codes or ordinances...

Страница 8: ...l charge 3m x 17g 51g additional charge This outdoor unit is designed for use only with indoor coils that utilize a TXV refrigerant metering device With an indoor TXV use the subcooling method to make...

Страница 9: ...wer motor When thermostat is satisfied its contacts open de energizing contactor and blower relay Compressor and motors stop NOTE If indoor unit is equipped with a time delay relay circuit the blower...