40

Troubleshooting Cont’d

Problem

Possible Cause

Possible Solution

Product too warm

Improper EPR Set Point

If SDC inlet temperature is above 28°F reduce the EPR set 

point

Improper Thermostat Bulb 

Location

Ensure that the thermostat bulb for the gravity coil (A) is not 

contacting any coil parts and is located in the discharge air 

stream

Improper TXV Bulb
Location

Ensure that the TX valve bulbs are located as per the piping 

diagram. Refer to Pipe Diagram

Improper Deck Plates 

(and Pans) Sitting

Ensure that the deck plates (and pans) are seated and 

making good contact with the SDC and each other

Gravity Coil Air Flow 

Obstruction

Ensure that gravity coil is fully cleared all the time

Defrost Failure To Clear 

All SDC Ice Buildup

The SDC will eventually pack with ice and refrigeration 

performance will be severely degraded.  Confirm Evaporator 

Temperature is 28°F, SDC T-Stat SP to specification, 

and SDC termination temperature reaching at least 42°F.  

Increase the defrost time in 5 minute increments if this 

condition is observed, and termination temperature not 

achieved.

Improperly sized 

refrigerant lines

Ensure that refrigerant lines are properly sized per the 

installation manual.  Inspect liquid line for kinks, pinched or 

excessive u-bends

Solid Column Of Liquid 

Refrigerant NOT reaching 

the TXV

Inspect liquid line for kinks, pinched or excessive u- bends.

Liquid Refrigerant case 

inlet Temperature is 

excessive

Ensure that the liquid refrigerant entering temperature is not 

excessive.  Liquid greater than 110°F at 6” ahead of the TXV 

may be an indication of equipment problems

Product Introduction 

Temperature Too High

Correct product introduction temperature should be 
34°F.-36°F.

Product Is Stacked Too 

High

Reduce display height of product.  Less than 6” is 

recommended

Product is displayed in 

containers that impede 

the conduction cooling 

from the SDC

Use containers with full length, flat bottoms.  Refer to 

MERCHANDIZING RECOMMENDATIONS (page 29) section 

for further information.

Incorrect replacement 

lighting is adding too 

much heat

Use only Hussmann genuine replacement parts or equivalent.

Case temperature is 

too warm.

Ambient conditions may 

be affecting the case 

operation.

Check case position in store. Is the case located near an 

open door, window, electric fan or air conditioning vent that 

may cause air currents? Case must be located minimum 

15 Ft away from doors or windows. Cases are designed to 

operate at or below 75°F Dry bulb and 55% relative humidity.

Discharge air temp is out 

of spec.

Check suction pressure and insure that it meets factory 

specifications.

Case is in defrost.

Check defrost settings. See Technical Specifications section.

Product load may be over 

its limits blocking airflow.

Redistribute product so it does not exceed load level.

Содержание VR3-HV-M Series

Страница 1: ...CIALTY U S E R M A N U A L 0 MERCHANDISER VR3 M HV M MEAT SERVICE VR3 VR3 M F 4 R VR3 M F 6 R VR3 M F 8 R VR3 M F 12 R VR3HV M F 4 R VR3HV M F 6 R VR3HV M F 8 R VR3HV M F 12 R VR3HV M F 10 R Remote 22...

Страница 2: ...017 y Compliant Table of Contents Electrical 22 Electrical Info Merchandiser Electrical Data 22 Electrical Connections 22 Field Wiring 22 of Wiring 22 Remove Rear Raceway 23 Electrical Conduit Electri...

Страница 3: ...Chino If such a shortage involves the carrier notify the carrier immediately and request an inspection Hussmann Chino will acknowledge shortages within ten days from receipt of equipment Hussmann Chi...

Страница 4: ...Case Sections 4...

Страница 5: ...ll equipment should be thoroughly examined for shipping damage before and during unloading This equipment has been carefully inspected at our factory Any claim for loss or damage must be made to the c...

Страница 6: ...monstrates perfect placement of a dollie per 1 side for both Base Legs of the merchandiser IF APPLICABLE NOT ALL CASES CARRY LEG BRACES Installation cont d Move the fixture as close as possible to its...

Страница 7: ...re long enough to support beyond the center of the case but not damage near components Check for proper balance before moving A minimum fork length of 36 is recommended for 68 wide cases Installation...

Страница 8: ...nt Adjust the legs at each corner of the case to level out any discrepancies in order to optimize case performance and proper drainage Note To avoid removing concrete flooring begin line up levelling...

Страница 9: ...E CORRECTLY WILL SOLVE MOST HINGE OPERATION PROBLEMS 1 Using case blueprints measure off and mark on the floor the exact dimensions of where the cases will sit Snap chalk line for front and back posit...

Страница 10: ...on Apply heavy amount to cover entire shaded area It is the contractor s responsibility to install case s according to local construction and health codes ATTENTION INSTALLER 5 Apply liberal bead of c...

Страница 11: ...front to back and side to side on inside bulkheads at joint 8 Attach sections together via the bolts pictured in the illustration below 9 Apply bead of butyl to top of bulk heads and slip on stainless...

Страница 12: ...rm to minimize sag from product IMPORTANT ATTEMPTING TO COMPEN SATE FOR POOR INSTALLATION PRACTIC ES BY MANIPULATING THE CANOPY HARD WARE WILL RESULT IN UNSATISFACTORY WORKMANSHIP AND POSSIBLY CAUSE H...

Страница 13: ...heck leveling for all cases Do not move lineup during adjustment LEFT RIGHT IN OUT UP DOWN UPPER LOWER HINGE ACCESS HINGE ASSEMBLY GLASS NOT SHOW HINGE ASSEMBLY GLASS NOT SHOW TURNING THE SCREWDRIVER...

Страница 14: ...f rear panel to Base Les as shown below Front Body Panel Install No tools will be needed to install body panels To begin Bottom panel assembly place the front panel along in front of the case and alig...

Страница 15: ...01 0628 16 FT L SEALANT BUTYL TUBE 100 01 0121 1 M ALIGNMENT PIN 0376408 3 N SPLINE H CHAN POLY 4 1 2 200 02 3022 1 O JOINING NYLON WASHER 2H04205800 1 P BOLT 3 8 16 X 1 5 300 03 0850 3 Q NUT 3 8 16 3...

Страница 16: ...ions are at the right hand end of the case as viewed from the front beneath the display pans The merchandiser will beforehand ensure an earlier cut hole through the pod to exit the merchandiser for th...

Страница 17: ...SCREW SHOULD BE MOUNTED BELOW COIL TUBE TOP SURFACE 3 SENSOR LOCATED 2 FROM TOP OF RSS AND 4 FROM END WALL NEAREST T STAT DIGITAL T STAT CNTL DIGITAL T STAT CNTL TXV TXV SUCTION SOLENOID FLTR DRYR OPT...

Страница 18: ...erview of the VR3HV M F C S EP Piping schematic Note Refrigeration components have been fitted with a component tray for ease in use of cleaning and maintenance under the deck pans SOLENOID HAND VALVE...

Страница 19: ...19 Piping schematic for Serpentine Coil and Gravity Coil Refrigeration cont d...

Страница 20: ...S 115 VOLT 4 2 6 7 15 0 2 16 0 2 28 0 1 10 0 3 39 0 9 100 1 115 15 6 4 6 7 15 0 5 32 0 4 44 0 1 15 0 5 59 1 3 150 1 115 15 8 4 6 7 15 0 5 32 0 5 57 0 2 21 0 7 77 1 7 200 1 115 15 10 4 6 7 15 0 5 32 0...

Страница 21: ...EATERS LED LIGHTS 115 VOLT 4 3 6 70 15 0 4 24 0 3 31 0 1 10 0 4 41 0 9 100 1 115 15 6 6 6 70 15 0 7 48 0 4 46 0 1 15 0 5 61 1 3 150 1 115 15 8 6 6 70 15 0 7 48 0 5 62 0 2 21 0 7 82 1 7 200 1 115 15 10...

Страница 22: ...ERES Field Wiring Field wiring must be sized for component am peres stamped on the serial plate refer to pg 16 for location Actual ampere draw may be less than specified Identification of Wiring Leads...

Страница 23: ...case Electrical Conduit Electrical Box The Merchandisers Electrical conduit can be found inside the compartment at the rear Re moving the raceway will gain access to the elec trical components inside...

Страница 24: ...IDE POWER 120 VAC 60 Hz 125 01 0443 BLK 14 WHT 14 GRN 14 ALL SINGLE RECEPTACLES TO BE TIED TO DUPLEX GFCI RECEPTACLE BUNDLE YELLOW 15 0 L1 120 V LOADING CIRCUIT 2 optional FRONT SECTION MCA 0 21A MOP...

Страница 25: ...01 0443 BLK 14 WHT 14 GRN 14 ALL SINGLE RECEPTACLES TO BE TIED TO DUPLEX GFCI RECEPTACLE BUNDLE YELLOW 15 0 L1 120 V LOADING CIRCUIT 2 optional 3 LED LIGHT FRONT SECTION MCA 0 31A MOP 15A 120 VAC 60...

Страница 26: ...3178 LOAD SIDE POWER 120 VAC 60 Hz 125 01 0443 BLK 14 WHT 14 GRN 14 ALL SINGLE RECEPTACLES TO BE TIED TO DUPLEX GFCI RECEPTACLE BUNDLE YELLOW 15 0 L1 120 V LOADING CIRCUIT 2 optional 4 LED LIGHT FRON...

Страница 27: ...60 Hz L1 N MCA 3 3A MOP 15A T STAT 1 225 01 0705A INCOMING POWER 120 VAC 60 Hz GFCI DUPLEX 125 01 3178 LOAD SIDE POWER 120 VAC 60 Hz 125 01 0443 BLK 14 WHT 14 GRN 14 ALL SINGLE RECEPTACLES TO BE TIED...

Страница 28: ...OWER 120 VAC 60 Hz 125 01 0443 BLK 14 WHT 14 GRN 14 ALL SINGLE RECEPTACLES TO BE TIED TO DUPLEX GFCI RECEPTACLE BUNDLE YELLOW 15 0 L1 120 V LOADING CIRCUIT 2 optional FRONT SECTION MCA 0 21A MOP 15A 1...

Страница 29: ...01 0443 BLK 14 WHT 14 GRN 14 ALL SINGLE RECEPTACLES TO BE TIED TO DUPLEX GFCI RECEPTACLE BUNDLE YELLOW 15 0 L1 120 V LOADING CIRCUIT 2 optional 3 LED LIGHT FRONT SECTION MCA 0 31A MOP 15A 120 VAC 60...

Страница 30: ...MING POWER 120 VAC 60 Hz GFCI DUPLEX 125 01 3178 LOAD SIDE POWER 120 VAC 60 Hz 125 01 0443 BLK 14 WHT 14 GRN 14 ALL SINGLE RECEPTACLES TO BE TIED TO DUPLEX GFCI RECEPTACLE BUNDLE YELLOW 15 0 L1 120 V...

Страница 31: ...OLENOID 225 01 0878 14A 120VAC GRAVITY COIL SUCTION SOLENOID 1H84576500 14A 120VAC T STAT 1H66770550 BUNDLE WHITE BLACK 120 VAC 60 Hz N L1 BLACK 14 WHITE 14 SENSOR BLK WHT STRIPE 14 WHITE 14 LN 120 LC...

Страница 32: ...C 60 Hz L1 N MCA 3 3A MOP 15A T STAT 1 225 01 0705A INCOMING POWER 120 VAC 60 Hz GFCI DUPLEX 125 01 3178 LOAD SIDE POWER 120 VAC 60 Hz 125 01 0443 BLK 14 WHT 14 GRN 14 ALL SINGLE RECEPTACLES TO BE TIE...

Страница 33: ...D LOAD LIMIT Basic Operation The VR3HV M F EP series case cools meat fish in two ways 1 The Spiral Deck Coil under the display deck cools the meat fish product by means of con tact conduction 2 The Gr...

Страница 34: ...weep Fans On Off switch only use if needed Store conditions if different from design condi tions may require adjustments to settings as listed in the SETUP TROUBLE SHOOTING sec tion Please refer publi...

Страница 35: ...increased product life optional refrigerated or dry storage DECK PAN Rotate product every several hours Bottom layer should be rotated to the top and flipped This ensures even cooling dehydration and...

Страница 36: ...are is designed with ridge along the bottom end or ridges across the sur face bottom for structural support Often times display ware has feet on the bottom of it to pre vent direct contact with the di...

Страница 37: ...se bleach Clean frequently to avoid build up of hard stub born stains A stainless steel cleaning solution may be used periodically to minimize scratching and remove stains Rinse and wipe dry immediate...

Страница 38: ...as much product as can be taken to the cooler in a timely manner First Turn off Refrigeration then discon nect electrical power to merchandiser Thoroughly clean all surfaces with soap and hot water Do...

Страница 39: ...surface of the Spiral Deck Tube at mid tube from outer inner of spiral to insure no interference with Deck Plate Band strap should be thin gauge copper GC T Stat sensor tip should be located approxim...

Страница 40: ...t NOT reaching the TXV Inspect liquid line for kinks pinched or excessive u bends Liquid Refrigerant case inlet Temperature is excessive Ensure that the liquid refrigerant entering temperature is not...

Страница 41: ...on Air Sweep Fans located at the right rear of merchandiser Water has pooled under case Case drain is clogged Clear drain PVC drains under case may have a leak Repair as needed Case tub has unsealed o...

Страница 42: ...other support contact your Hussmann representative Please include the model and serial number of the product Hussmann Corporation Corporate Headquarters Bridgeton Missouri 63044 2014 Hussmann Warranty...

Отзывы:

Похожие инструкции для VR3-HV-M Series