The Flooding Charges listed in the table
above reflect additional refrigerant required
for split condenser method of winter control
above normal summer operating charge and
heat reclaim coil requirements.
N o t e : Condenser ambient should be noted
when determining the flooding charge.
• If above 65˚F, add the specified amounts
of refrigerant when the system stabi-
lizes after start-up.
• If below 65˚F but above the coldest
expected, some condenser flooding
will already be occurring and required
additional charge will be lower.
• If the coldest expected temperature is
above 20˚F, the flooding char g e
required will be less than 50% of each
condenser circuit.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 • Printed in USA
Revised August 1, 1996
P/N 340272A
5 - 3
Physical Data
Weight /w
Max Flood
Inlet/Outlet
No.
FLA 3PH
Max. Flood
Charge
Connections
Model
Fans
(lbs)
(lbs)
OD
R404A/
R404A/
208V 230V 460V
R22
R507
R22
R507
1x1
2.8
2.6
1.3
205
221
19
35
1
1/8
HLCVB
1x2
5.6
5.2
2.6
410
445
40
75
1
3/8
*
1x3
8.4
7.8
3.9
615
666
59
110
1
3/8
1x4
11.2
10.4
5.2
925
1002
88
165
1
5/8
1x5
14.0
13.0
6.5
1039
1125
99
185
2
1/8
1x6
16.8
15.6
7.8
1239
1343
119
223
2
1/8
1x7
19.6
18.2
9.1
1551
1679
147
275
2
5/8
1x2
8.8
8.0
4.0
1081
1137
64
120
1
5/8
HLCVF
1x3
13.2
12.0
6.0
1574
1658
96
180
2
1/8
1x4
17.6
16.0
8.0
2240
2352
128
240
1
5/8
HLCVG
1x5
22.0
20.0
10.0
3020
3231
242
453
2
5/8
1x6
26.4
24.0
12.0
3555
3809
291
545
2
5/8
2x2
11.2
10.4
5.2
820
897
88
165
1
3/8
*
HLCVI
2x3
16.8
15.6
7.8
1230
1334
119
223
1
3/8
2x4
22.4
20.8
10.4
1850
2003
176
329
1
5/8
2x5
28.0
26.0
13.0
2078
2263
212
397
2
1/8
2x6
33.6
31.2
15.6
2420
2627
237
444
2
1/8
2x7
39.2
36.4
18.2
3075
3332
295
552
2
5/8
2x2
17.6
16.0
8.0
2001
2113
128
240
1
5/8
HLCVV
2x3
26.4
24.0
12.0
2889
3055
191
357
2
1/8
2x4
35.2
32.0
16.0
3733
3955
255
477
2
1/8
HLCVW
2x5
44.0
40.0
20.0
5020
5433
474
887
2
5/8
2x6
52.8
48.0
24.0
6030
6527
570
1067
2
5/8
*Inlet = 1
3/8
, Outlet = 1
1/8
O
N
E
F
A
N
W
I
D
E
T
W
O
F
A
N
S
W
I
D
E
Содержание Super Plus
Страница 1: ......
Страница 22: ...REFRIGERATION PROCESS Revised August 1 1996 2 2 HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ...
Страница 36: ...Revised August 1 1996 P N 340272A 3 5 HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ...
Страница 50: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ELECTRICAL Revised August 1 1996 4 10 ...
Страница 64: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ELECTRICAL Revised August 1 1996 4 24 ...
Страница 66: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ELECTRICAL Revised August 1 1996 4 26 ...
Страница 78: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA Revised August 1 1996 P N 340272A 5 5 ...
Страница 116: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA CONTROL SETTINGS Revised August 1 1996 8 8 ...
Страница 142: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA Addendum April 15 1997 P N 340272A A 7 ...
Страница 143: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA CONDENSER INSTALLATION Addendum April 15 1996 A 8 ...
Страница 144: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA Addendum April 15 1997 P N 340272A A 9 ...
Страница 145: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA CONDENSER INSTALLATION Addendum April 15 1996 A 10 ...
Страница 146: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA Addendum April 15 1997 P N 340272A A 11 ...
Страница 147: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA CONDENSER INSTALLATION Addendum April 15 1996 A 12 ...