Through Walls or Floors
Refrigeration lines run through walls or floors
must be properly insulated. Avoid running lines
through the refrigeration cases. When this is
done the lines must be adequately insulated—
Armaflex or equivalent.
From Machinery to Solid Object
When mounting lines from machinery to a
solid object allow line freedom for vibration
to prevent metal fatigue.
P-Trap Construction
A P-Trap must be installed at the bottom of all
suction risers to return oil to the compressors.
Reduced Riser
When a reduced riser is necessary, place the
reduction coupling downstream of the P-Trap.
Factory Supplied Stubs
Stub sizes provided from the Manifolds do not
automatically correspond to the line sizes nec-
e s s a r y. It is the installer’s responsibility to
supply reduction couplings.
Protecting Valves and Clamps
When brazing near factory installed clamps or
valves, be sure to protect them with a wet rag
to avoid overheating.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 • Printed in USA
COMPONENT PIPING
Revised August 1, 1996
3 - 2
Содержание Super Plus
Страница 1: ......
Страница 22: ...REFRIGERATION PROCESS Revised August 1 1996 2 2 HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ...
Страница 36: ...Revised August 1 1996 P N 340272A 3 5 HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ...
Страница 50: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ELECTRICAL Revised August 1 1996 4 10 ...
Страница 64: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ELECTRICAL Revised August 1 1996 4 24 ...
Страница 66: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA ELECTRICAL Revised August 1 1996 4 26 ...
Страница 78: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA Revised August 1 1996 P N 340272A 5 5 ...
Страница 116: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA CONTROL SETTINGS Revised August 1 1996 8 8 ...
Страница 142: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA Addendum April 15 1997 P N 340272A A 7 ...
Страница 143: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA CONDENSER INSTALLATION Addendum April 15 1996 A 8 ...
Страница 144: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA Addendum April 15 1997 P N 340272A A 9 ...
Страница 145: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA CONDENSER INSTALLATION Addendum April 15 1996 A 10 ...
Страница 146: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA Addendum April 15 1997 P N 340272A A 11 ...
Страница 147: ...HUSSMANN CORPORATION BRIDGETON MO 63044 2483 Printed in USA CONDENSER INSTALLATION Addendum April 15 1996 A 12 ...