             The timer will need to be reset after a fail-
ure of the power supply, or if the power is turned 
off for an extended period of time. 
 
             The defrost cycle is time initiated-
temperature terminated.  The defrost stat is lo-
cated on the left hand side of the evaporator, on a 
return  bend of the tubing  near  the  rear of  the 
evaporator.  When the stat sens es a temperature 
of 58ºF / 14ºC the defrost cycle is terminated.  If 
the stat should fail, then defrost is terminated by 
the failsafe setting on the timer. 
 
TEMPERATURE CONTROL –  
 
              The temperature control is located in the 
electrical enclosure.  The control  is factory pre-
set to maintain ice cream storage temperatures.  
Turning the control clockwise will derive colder 
temperatures .  The sensing tube for the control is 
mounted on the cabinet interior rear wall.  Access 
to the tube is gained by removing the interior 
rear wall panel . 
 
CONDENSER –  
 
              The fin and tube condenser requires peri-
odic cleaning.  To clean the condenser, remove 
the front access panel.  Using a soft brush, re-
move the dirt and lint off the fins.  A vacuum or 
compressed air may also be used.  NEVER USE 
A HARD OBJECT TO CLEAN THE F INS AS 
DAMAGE TO THE CONDENSER MAY OC-
CUR!!   
 
              A regular schedule should be established 
for the cleaning of the condenser.  Failure to keep 
the condenser clean will result in premature com-
pressor failure and/ or efficiency loss.  Location of 
the cabinet in the store and store traffic should be 
considered when setting up this s chedule. 
 
 

TEMPERATURE CONTROL 
                          REPLACEMENT  - 
 

              

If there is product in the cabinet, it 

must be placed in a storage freezer. Discon-
nect power to the cabinet. Remove the front 
and left side access panels. Remove electri-
cal enclosure cover. Remove the knob on the 
control  and the two screws holding the plate 
and control body in place. Remove the flag 
connections from the control. Remove the 
interior bottom pans and the rear interior 
wall.  
 
             The wall has two screws, one in each 
upper corner, holding it in pl ace. The sens -
ing bulb for the control is clamped to the 
rear wall. Remove the clamp and replace the 
control. Assemble in reverse  order,  reset 
timer,  and reconnect the power supply. Al-
low the cabinet to pull down to proper tem-
perature before reloading. 
 
DEFROST STA T REPLACEMENT - 
 
Remove product from cabinet and place in 
another freezer. Disconnect power to the 
cabinet. Remove front and left side access 
panels. Remove electrical enclosure cover. 
Remove proper wires from stat connected to 
terminal board. Remove interior bottom 
pans. Remove stat from return bend on 
evaporator coil and install new stat making 
s ure retaining clip holds stat to tubing 
tightly. Cut wires from old stat and tape 
wires to new  stat wires. Gently pull  old 
wires guiding wires through hole penetra-
tion in bottom of case. Connect new wires to 
corres ponding numbers on terminal board. 
Reset timer and reconnect power to cabinet. 
Allow cabinet to pull down to proper tem-
perature before loading. 

 

 
 
 

Содержание GGSM

Страница 1: ...MERCHANDISER Low Temperature Glass Front and Sides P N OII GGSM January 2006 First Call for help US and Canada 1 800 922 1919 Soporte T cnico y Asistencia M xico 01 800 522 1900 For a Service Network...

Страница 2: ...and Circulation 4 Glass Heaters 5 Electric Condensate Pan 5 Defrost Time Clock 5 Temperature Control 6 Temperature Control Replacement 6 Condenser 6 Defrost Stat Replacement 6 Glass Heater Wire Repla...

Страница 3: ...Loca tions where direct sunlight would shine into the cabinet for extended periods of time and locations where drafts from open doors air conditioning ducts fans and grills would blow into the cabinet...

Страница 4: ...d the lower left access panel Ac cess to the enclosure is accomplished by first removing the front access panel and then the side panel There are two screws in each end of this panel The electrical en...

Страница 5: ...rmostat built into the heater The drain car rying water to this pan should be trapped to prevent warm air migrating back to the evapo rator Defrosting of the evaporator is accom plished through the us...

Страница 6: ...cation of the cabinet in the store and store traffic should be considered when setting up this schedule TEMPERATURE CONTROL REPLACEMENT If there is product in the cabinet it must be placed in a storag...

Страница 7: ...wires Gently pull wires through hole penetration in bottom of cabinet and connect to proper terminals on ter minal board Reset timer and reassemble cabi net in reverse order BULB BALLAST REPLACEMENT...

Страница 8: ...ing 2 Relay defective 2 Replace Compressor will not start no hum 1 Power disconnected 1 Reconnect power 2 Power switch off 2 Reposition switch to ON 3 Blown or tripped breaker 3 Reset breaker 4 Defect...

Страница 9: ...ossible defrost heater joints grounded or time clock defective 5 Repair replace Low head and suction pressure 1 Short of refrigerant 1 Leak check change drier evacuate and recharge 2 Restricted cap tu...

Страница 10: ...er will not come on until the defrost thermostat temperature has been reduced below 32 F 0 C Defrost cycle too long 1 Terminating on timer failsafe factory set 40 mins 1 Replace defrost thermostat The...

Страница 11: ...ctory until such time as the defective part is returned and proved to be defective by our Quality Control De partment v Contact your Hussmann Distributor for instructions on returning in warranty part...

Страница 12: ...be given too partially offset the invoice for the replacement To obtain reimbursement forward to Hussmann Corporation 140 East State Street Gloversville NY 12078 the following information The cabinet...

Страница 13: ...IED FRACTIONAL 1 32 DECIMAL 0 031 ANGULAR 1 HOLE LOCATION SPACING 1 64 1 2 3 4 5 6 17 18 19 20 21 22 23 24 BLK 3 4 X N 2 1 S1 S3 POWER SWITCH POWER CORD COMPRESSOR CONDENSER FAN 2 R GGSM 3 DEFROST T S...

Отзывы: