1-6
I
nstallatIon
P/N 0515957_M
U.S. & Canada 1-800-922-1919 • Mexico 01 800-890-2900 • www.hussmann.com
Hussmann Self-Contained Refrigeration Equipment Start Up Check List
Hussmann Corporation, 12999 St Charles Rock Road, Bridgeton, MO 63044-2483 U.S.A.
Email: [email protected] Fax: 866-443-1254
Today’s Date
Store Name and Number
Store Address
Unit Model Number
Unit Serial Number
Contractor/Technician
Startup activity
Record date of completion or
requested data (i.e., voltage,
measurements, instrument readings).
Locate, read and maintain install/operation manual in a safe place for future reference.
Examine unit. Confirm there is NO damage
or concealed damage
.
Level the unit, side to side and front to rear.
Remove all shipping brackets/
compressor
straps/bolts etc.
Unit must be run on a dedicated electrical circuit without the use of an extension cord.
Record supply voltage at outlet with unit off.
Volts -
Verify refrigerant lines are properly secured and not touching or rubbing other lines, wires or frame work.
Verify fan motors and motor mounts are tight.
Verify fan blade/s are tight and are not rubbing/contacting other components.
Verify field and factory electrical connections are tight.
Verify electrical connections at lamps are tight and secure.
Verify all electrical wiring is secured and clear of any sharp edges or hot lines.
Verify there any no visible oil or refrigerant leaks.
Verify the condensate drain line is properly trapped and pitched.
What are the clearances on the sides and back of unit?
Left Side -
Right Side -
Back -
Top -
Are there any air disturbances external to the unit
?
Heat and air registers, fans, and doors etc.
Start up unit, record total unit amp draw after 5 minutes of operation.
Total unit amps -
Record compressor amp draw.
Amps -
Record anti-sweat heater amp draw if applicable
Amps -
N/A
Record voltage reading with unit running.
Volts -
Verify condenser and evaporator fans are working
Is condenser air inlet or air exhaust restricted or recirculating?
Record ambient conditions around unit (wet Bulb temperature and dry bulb temperature) and RH%
Wet Bulb °F
Dry Bulb
°F
RH%
Record condenser air inlet temp (
center of the coil)
°F
Record condenser air outlet temp
(right after the fan motor)
°F
After unit reaches operating temperature, record unit discharge air temperature (
center of the flue).
°F
After unit reaches operating temperature, record unit return air temperature
(center of flue).
°F
Does unit controller operate properly? See controller or I/O manual for proper controller operation.
Record defrost heater amp draw (
when applicable)
.
Amps -
Verify there are no visible water leaks.
Verify door switches work correctly, turning evap fans on and off.
Verify unit doors and lids work and are fully sealed.
Verify that all the panels, shields and covers are in place.
Confirm the unit has no vibrations or abnormal noise.
Advise owner/operator that merchandiser must operate at temperature for 24 hrs prior to loading with product.
Technician Notes:
Form HSCW01 Rev. 30MAY12
P/N 0525209_B
LEGAL DISCLAIMER:
Hussmann shall not be liable for any repair or replacements made without the written consent of Hussmann, or when the product is installed or operated in a
manner contrary to the printed instructions covering installation and service which accompanied such product.