CoreLink
TM
30
P/N 3128012_A
U.S. & Canada 1-800-922-1919 • Mexico 1-800-890-2900 • WWW.HUSSMANN.COM
5.8
Super Heat setting, C0: More: Superheat:
•
Navigate to C0: More and then to Super heat to check SH setpoints, Min valve Position,
Max valve position, MOP & LOP
•
Superheat Parameters verification:
Navigate to C0: More and then to Super heat setpoints to verify following 15R/W
parameters
E2 Parameter
CoreLink Parameter
Description
Range
SH_Setpoint1
SH1
Superheat EVAP 1 setpoint
(1 to 40) °F
SH_Setpoint2
SH2
Superheat EVAP 2 setpoint
(1 to 40) °F
SH_Setpoint3
SH3
Superheat EVAP 3 setpoint
(1 to 40) °F
MAX_OpPress1(T)
Max Operating Pressure 1 Max EVAP 1 Operating Pressure Threshold
(-90 to 90) °F
MAX_OpPress2(T)
Max Operating Pressure 2 Max EVAP 2 Operating Pressure Threshold
(-90 to 90) °F
MAX_OpPress3(T)
Max Operating Pressure 3 Max EVAP 3 Operating Pressure Threshold
(-90 to 90) °F
MIN_VALVEPOS1
Min valve Position 1
MIN Valve Pos for Section 1
(0-100) %
MIN_VALVEPOS2
Min Valve Position 2
MIN Valve Pos for Section 2
(0-100) %
MIN_VALVEPOS3
Min valve Position 3
MIN Valve Pos for Section 3
(0-100) %
MIN_OpPresS1(T)
Low Operating Pressure 1 Min EVAP 1 Operating Pressure Threshold
(-90 to 90) °F
MIN_OpPress2(T)
Low Operating Pressure 2 Min EVAP 2 Operating Pressure Threshold
(-90 to 90) °F
MIN_OpPress3(T)
Low Operating Pressure 3 Min EVAP 3 Operating Pressure Threshold
(-90 to 90) °F
MAX_VALVEPOS1
Max Valve Position 1
Max Valve Pos for Section 1
(0-100) %
MAX_VALVEPOS2
Max Valve Position 2
Max Valve Pos for Section 2
(0-100) %
MAX_VALVEPOS3
Max Valve Position 3
Max Valve Pos for Section 3
(0-100) %