49
20
Manual RS8EP502 © Danfoss 12-2015
AK-CC 210
Menu survey
SW = 2.3x
Parameters
EL-diagram number (page 6)
Min.-
value
Max.-
value
Factory
setting
Actual
setting
Function
Codes
1
2
3
4
5
6
7
8
9
10
Normal operation
Temperature (set point)
---
-50.0°C
50.0°C
2.0°C
Thermostat
Differential
***
r01
0.1 K
20.0K
2.0 K
Max. limitation of setpoint setting
***
r02
-49.0°C
50°C
50.0°C
Min. limitation of setpoint setting
***
r03
-50.0°C
49.0°C
-50.0°C
Adjustment of temperature indication
r04
-20.0 K
20.0 K
0.0 K
Temperature unit (°C/°F)
r05
°C
°F
°C
Correction of the signal from S4
r09
-10.0 K
+10.0 K
0.0 K
Correction of the signal from S3
r10
-10.0 K
+10.0 K
0.0 K
Manual service, stop regulation, start regulation (-1, 0, 1)
r12
-1
1
0
Displacement of reference during night operation
r13
-10.0 K
10.0 K
0.0 K
Definition and weighting, if applicable, of thermostat sensors
- S4% (100%=S4, 0%=S3)
r15
0%
100%
100%
The heating function is started a number of degrees below the
thermostats cutout temperature
r36
-15.0 K
-3.0 K
-15.0 K
Activation of reference displacement r40
r39
OFF
ON
OFF
Value of reference displacement (activate via r39 or DI)
r40
-50.0 K
50.0 K
0.0 K
Alarm
Delay for temperature alarm
A03
0 min
240 min
30 min
Delay for door alarm
***
A04
0 min
240 min
60 min
Delay for temperature alarm after defrost
A12
0 min
240 min
90 min
High alarm limit
***
A13
-50.0°C
50.0°C
8.0°C
Low alarm limit
***
A14
-50.0°C
50.0°C
-30.0°C
Alarm delay DI1
A27
0 min
240 min
30 min
Alarm delay DI2
A28
0 min
240 min
30 min
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A36
0%
100%
100%
Compressor
Min. ON-time
c01
0 min
30 min
0 min
Min. OFF-time
c02
0 min
30 min
0 min
Time delay for cutin of comp.2
c05
0 sec
999 sec
0 sec
Compressor relay 1 must cutin and out inversely
(NC-function)
c30
0
OFF
1
ON
0
OFF
Defrost
Defrost method (none/EL/GAS/BRINE)
d01
no
bri
EL
Defrost stop temperature
d02
0.0°C
25.0°C
6.0°C
Interval between defrost starts
d03
0 hours
240
hours
8 hours
Max. defrost duration
d04
0 min
180 min
45 min
Displacement of time on cutin of defrost at start-up
d05
0 min
240 min
0 min
Drip off time
d06
0 min
60 min
0 min
Delay for fan start after defrost
d07
0 min
60 min
0 min
Fan start temperature
d08
-15.0°C
0.0°C
-5.0°C
Fan cutin during defrost
0: Stopped
1: Running
2: Running during pump down and defrost
d09
0
2
1
Defrost sensor (0=time, 1=S5, 2=S4)
d10
0
2
0
Pump down delay
d16
0 min
60 min
0 min
Drain delay
d17
0 min
60 min
0 min
Max. aggregate refrigeration time between two defrosts
d18
0 hours
48 hours
0 hours
Defrost on demand - S5 temperature’s permitted variation dur-
ing frost build-up. On c
entral plant choose 20 K (=off )
d19
0.0 K
20.0 k
20.0 K
Delay of hot gas defrost
d23
0 min
60 min
0 min
Fan
Fan stop at cutout compressor
F01
no
yes
no
Delay of fan stop
F02
0 min
30 min
0 min
Fan stop temperature (S5)
F04
-50.0°C
50.0°C
50.0°C
HACCP
Actual temperature measurement for the HACCP function
h01
Last registered peak temperature
h10
Selection of function and sensor for the HACCP function. 0 = no
HACCP function. 1 = S4 used (maybe also S3). 2 = S5 used
h11
0
2
0
Alarm limit for the HACCP function
h12
-50.0°C
50.0°C
8.0°C
Time delay for the HACCP alarm
h13
0 min.
240 min.
30 min.
Select signal for the HACCP function. S4% (100% = S4, 0% = S3)
h14
0%
100%
100%
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
t01-t06
0 hours
23 hours
0 hours
Six start times for defrost.
Setting of minutes.
0=OFF
t11-t16
0 min
59 min
0 min
Clock - Setting of hours
***
t07
0 hours
23 hours
0 hours
Clock - Setting of minute
***
t08
0 min
59 min
0 min
Clock - Setting of date
***
t45
1
31
1
Clock - Setting of month
***
t46
1
12
1
Clock - Setting of year
***
t47
0
99
0
Miscellaneous
Delay of output signals after start-up
o01
0 s
600 s
5 s
Содержание Chino RDI-20
Страница 8: ...8...
Страница 9: ...0...
Страница 20: ...20 Wiring Diagram Cont d 0 1 2 2 2 3 4 4 1 AK CC 210 N M...
Страница 21: ...21 Wiring Diagram Cont d 0 1 2 2 2 3 4 4 1 AK CC 210 N M...
Страница 22: ...22 Wiring Diagram Cont d 0 1 2 2 2 3 4 4 1 AK CC 210 N M 5 15A 6...
Страница 23: ...23 0 1 2 2 2 3 4 4 1 AK CC 210 N M Wiring Diagram Cont d...
Страница 24: ...24 0 1 2 2 2 3 4 4 1 AK CC 210 N M Wiring Diagram Cont d...
Страница 30: ...30 Controller for temperature control AK CC 210 User Guide ADAP KOOL Refrigeration control systems...