background image

Rev. 0506 

5

Plumbing

WASTE OUTLET AND P-TRAP

The waste outlet is located off the center of the case 

on one side allowing drip piping to be run lengthwise 

under the fixture.

A 1-1/2” P-trap and threaded adapter are supplied with 

each fixture. The P-trap must be installed to prevent 

air leakage and insect entrance into the fixture.

NOTE:  PVC-DWV solvent cement is recommended. 

Follow the manufacturer’s instructions.

INSTALLING CONDENSATE DRAIN

Poorly  or  improperly  installed  condensate  drains 

can seriously interfere with the operation of this re-

frigerator, and result in costly maintenance and prod-

uct losses. Please follow the recommendations listed 

below when installing condensate drains to insure a 

proper installation:

1.  Never use pipe for condensate drains smaller 

than the nominal diameter of the pipe or P-trap 

supplied with the case.

2.  When connecting condensate drains, the P-trap 

must be used as part of the condensate drain 

to prevent air leakage or insect entrance. Store 

plumbing system floor drains should be at least 

14” off the center of the case to allow use of the 

P-trap pipe section. Never use two water seals 

in series in any one line. Double P-traps in se-

ries will cause a lock and prevent draining.

3.  Always provide as much down hill slope (“fall”) 

as possible; 1/8” per foot is the preferred mini-

mum. PVC pipe, when used, must be supported 

to maintain the 1/8” pitch and to prevent warp-

ing.

4.  Avoid long runs of condensate drains. Long 

runs make it impossible to provide the “fall” nec-

essary for good drainage.

5.  Provide a suitable air break between the flood 

rim of the floor drain and outlet of condensate 

drain. 1” is ideal.

6.  Prevent condensate drains from freezing:

a. Do not install condensate drains in contact 

with non-insulated suction lines. Suction lines 

should be insulated with a nonabsorbent insu-

lation material such as Armstrong’s Armaflex.

b. Where condensate drains are located in dead 

air spaces (between refrigerators or between 

a refrigerator and a wall), provide means to 

prevent freezing. The water seal should be 

insulated to prevent condensation.

DIPPER WELL

An optional NSF approved dipper well may be installed 

on the back of case.  The exact location of the dipper 

well will be determined by the customer.

1. Ensure dipper well is properly sealed by 

applying NSF certified silicone to seam between 

dipper well and back cover of case. 

2. The plumbing required must be done by a 

certified plumber.

Refrigeration

GELATO/SOFT ICE CREAM

These display cases are designed to hold product at 

temperatures that will allow operators to scoop or dip 

gelato and soft ice cream into cones, containers or 

dishes. The temperatures will fall in the range of plus 

4F to plus 12F depending on amount of sugar and 

butterfat in product. The temperature and condition 

of product must be checked after being in case the 

first four hours of operation. Because of the sensitive 

condition of these products, defrost is very critical. The 

fans do NOT run during defrost periods. The maximum 

time is 20 minutes for electric and 10 minutes for hot 

gas and Kool Gas. The fans are on a 2 minute delay 

after defrost to avoid adding heat to case. 

If, because of ambient conditions, the defrost must be 

changed, amount of defrosts not time is necessary. 

i.e., 3 by 20 minutes instead of 2 x 40 minutes.

REFRIGERANT TYPE

The standard refrigerant will be R-404 unless other-

wise specified on the customer order. Check the serial 

plate on the case for information.

Piping  for  more  than  one  case  on  a  condensing 

unit is run underground with either common suction 

and liquid lines from the machine room or individual 

suction and liquid lines joined together in the machine 

room. 

REFRIGERATION LINES 

 

 LIQUID    

  SUCTION

  

3/8”  O.D. 

 5/8” O.D.

NOTE: The standard coil is piped at 5/8” (suction); however, the store 

tie-in may vary depending on the number of coils and the draw 
the case has. Depending on the case setup, the connecting 
point in the store may be 

5

/

8

”, 

7

/

8

”, or 1

1

/

8

”. Refer to the particular case you are hooking up.

Refrigerant lines should be sized as shown on the 

refrigeration legend furnished by the store.

Install 

P-traps

 (oil traps) at the base of all suction line 

vertical risers.

Pressure drop

 can rob the system of capacity. To keep 

the pressure drop to a minimum, keep refrigerant line 

Содержание ASC-LG

Страница 1: ...ASC LG ASCS LG Rev 0506 Installation Operation Manual ASC LG ASCS LG Lift up Curved Glass Refrigerated Service Gelato and Ice Cream Case INSTALLATION OPERATION GUIDE ASC LG ASCS LG 0506...

Страница 2: ...CHINO PRODUCT CONTROL The serial number and shipping date of all equipment has been recorded in Hussmann s files for warranty and replacement part purposes All correspondence pertaining to warranty o...

Страница 3: ...ow be lifted off the crate skid Lift only at base of stand EXTERIOR LOADING These models have not been structurally designed to support excessive external loading Do not walk on their tops This could...

Страница 4: ...sed under leg or by use of 2x6 or 2x4 leg brace Remove side and back leg braces after case is set 3 Set second case as close as possible to the first case and level case to the first using the instruc...

Страница 5: ...l should be insulated to prevent condensation DIPPER WELL An optional NSF approved dipper well may be installed on the back of case The exact location of the dipper well will be determined by the cust...

Страница 6: ...on valves will be installed on the coil inlet coil outlet and in the discharge air Some supermarkets require a 4th sensor in the return air Case controllers will be located in the electrical race way...

Страница 7: ...Rev 0506 Paragon ERC 2 Programming Settings Instructions...

Страница 8: ...ASC LG ASCS LG 0506 Paragon ERC 2 Programming Settings Instructions Cont d...

Страница 9: ...Rev 0506 Paragon ERC 2 Programming Settings Instructions Cont d...

Страница 10: ...ASC LG ASCS LG 0506 10 Paragon ERC 2 Programming Settings Instructions Cont d...

Страница 11: ...pere draw may be less than specified Field wiring from the refrigeration control panel to the merchandisers is required for refrigeration thermostats Most component amperes are listed in the Case Spec...

Страница 12: ...void the use of supplemental flood or spot lighting Display light intensity has been designed for maximum visibility and product life at the factory The use of higher output fluorescent lamps H O and...

Страница 13: ...ss from improper caustic solutions is irreparable In addition to cleaning the glass with the recommended product there are precautions that should be taken when working and cleaning the inside of the...

Страница 14: ...cking case will affect its proper operation Make sure that the product is not higher then the discharge air of the case and does not block the center return air grill 6 Make sure all front glass is pr...

Страница 15: ...TRUCTIONS In order to replace or adjust the glass the glass must be placed in the raised position The underside of the clamp is exposed revealing the tightening screws By turning these screws counterc...

Страница 16: ...5 120 5 Forced 41 2 4 16 1 0 72 1 04 3 05 15 0 3 13 Air Axial 208V ASC LG ASCS LG Ice Cream Electric Defrost Option 4 450 1 800 30 10 20 150 20 Forced 41 2 1 30 2 0 18 0 35 1 83 15 65 15 0 1 04 Air Ax...

Страница 17: ...SENSOR ELECT T STAT 225 01 3355A NC C NO 240V COM 120V _ SENSOR DELAY RELAY 208 VOLT COIL MARS 90342 25 01 1342 4 REFRIGERATION 3 DEFROST L2 L1 G AIR SWEEP WARMER WIRE 125 01 3032 180w 115V L WARMER...

Страница 18: ...RS 6 450W 115VAC BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L L LIGHT SWITCH BACK COIL FRONT COIL NC C NO 240V COM 120V _ SENSOR SENSO...

Страница 19: ...G FAN DELAY LIMIT SWITCH 225 01 2046 REAR CHANNEL 125 01 0767 10W FT 115V 8 FT EVAPORATOR FAN 2 GE 9W 115V 00001212 M M DEFROST HEATER LIMIT SWITCH 600 22 0050 DRAIN HEATER 1 240W 208 V 125 02 1104 DE...

Страница 20: ...SPX30 2 F25T8 SPX30 1 F32T8 SPX30 LIGHT SWITCH DRAIN HEATER 1 300W 208 V DEFROST HEATERS 6 750W 208VAC BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FU...

Страница 21: ...BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L CAP CANOPY LIGHTS 6 F32T8 SPX30 NOSE LIGHTS 3 F32T8 SPX30 LIGHT SWITCH BUNDLE COLOR ORANG...

Страница 22: ...2912T 230VAC DISPLAY UNIT DEFROST TIMER 230V 50 60 Hz 125 01 2301 AIR TEMP DEFROST TEMP 125 01 2301A MAX 16 FEET N GROUND FAN COMP 1 DEFROST W G BK L AIR SWEEP HEATER W 120 VAC 125 01 ANTI SWEAT SWITC...

Страница 23: ...LAY UNKIT OMNI STAT 230V 50 60 Hz 952912T 125 01 2301 AIR TEMP DEFROST TEMP 125 01 2301A MAX 16 FEET N GROUND FAN COMP 1 DEFROST W G BK L AIR SWEEP HEATER W 120 VAC 125 01 ANTI SWEAT SWITCH 125 01 031...

Страница 24: ...EATER W 120 125 01 ANTI SWEAT SWITCH 125 01 0311 DUPLEX RECEPTACLE LEVITON 5320 W 125 01 0096 AIR SWEEP FAN MOTORS 2 125 01 3142 A M M RJ 45 NETWORK JACK 125 01 0200 125 01 0203 125 01 0204 PUMP DOWN...

Страница 25: ...25 01 0096 AIR SWEEP FAN MOTORS 2 125 01 3142 A M M RJ 45 NETWORK JACK 125 01 0200 125 01 0203 125 01 0204 PUMP DOWN SOLENOID 225 01 3206 NC L PUMP DOWN SWITCH 125 01 0311 L DRAIN HEATER RELAY COIL 20...

Страница 26: ...RECEPTACLE LEVITON 5320 W 125 01 0096 AIR SWEEP FAN MOTORS 2 125 01 3142 A M M RJ 45 NETWORK JACK 125 01 0200 125 01 0203 125 01 0204 PUMP DOWN SOLENOID 225 01 3206 NC L PUMP DOWN SWITCH 125 01 0311 L...

Страница 27: ...20 L CANOPY LIGHTS 2 F32T8 SPX30 NOSE LIGHTS 1 F32T8 SPX30 LIGHT SWITCH POWER REQUIRED 115 VAC 50 60 Hz 1 3 WIRE BALLAST 125 01 3266 FULHAM LH3 120 L CAP CAP ELECT T STAT 225 01 3355A SENSOR NC C NO 2...

Страница 28: ...25T8 SPX30 LIGHT SWITCH POWER REQUIRED 115 VAC 50 60 Hz 1 3 WIRE BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L ELECT T STAT 225 01 3355...

Страница 29: ...01 3266 FULHAM LH3 120 L CANOPY LIGHTS 4 F32T8 SPX30 NOSE LIGHTS 2 F32T8 SPX30 LIGHT SWITCH POWER REQUIRED 115 VAC 50 60 Hz 1 3 WIRE BALLAST 125 01 3266 FULHAM LH3 120 L ELECT T STAT 225 01 3355A SEN...

Страница 30: ...F32T8 SPX30 NOSE LIGHTS 2 F25T8 SPX30 1 F32T8 SPX30 LIGHT SWITCH POWER REQUIRED 115 VAC 50 60 Hz 1 3 WIRE BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266...

Страница 31: ...M LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L BALLAST 125 01 3266 FULHAM LH3 120 L CAP CANOPY LIGHTS 6 F32T8 SPX30 NOSE LIGHTS 3 F32T8 SPX30 LIGHT SWITCH DRAIN...

Страница 32: ...T DEFROST TIMER DISPLAY UNIT 115V 60 Hz 125 01 2304 AIR TEMP DEFROST TEMP 125 01 2301A MAX 16 FEET N GROUND FAN COMP 1 DEFROST PUMP DOWN SOLENOID 225 01 3206 NC L PUMP DOWN SWITCH 125 01 0311 L BALLAS...

Страница 33: ...aller is responsible for the proper installation of the system which dispenses condensate waste through an air gap into the building indirect waste system 1 4 The installer should perform a complete s...

Страница 34: ...for the following 1 Has the refrigerator been loaded with warm product 2 Is the product loaded beyond the Safe Load Line markers 3 Are the return air ducts blocked 4 Are the entering air ducts blocke...

Страница 35: ...during periods of inactivity f Minimize the transfer time of perishables from storage to display g Keep meat under refrigeration in meat cut ting and processing area except for the few moments it is b...

Страница 36: ...for your particular unit They can be found on a small metal plate on the unit Please note them below for future reference MODEL SERIAL NUMBER Additional copies of this publication may be obtained by...

Отзывы: