HW130 

–HW160 Hot Water Boilers 

 

14 

 

6.2 

GAS PIPE SIZING TABLES 

 

Natural gas at 1.13 kPa gas meter pressure 
VICTORIA 
Maximum run of copper pipe with average number of fittings 

Model 

20 mm 

25 mm 

32 mm 

40 mm 

50 mm 

HW130 

4 m 

25 m 

90 m 

260 m 

320 m 

HW160 

2 m 

14 m 

50 m 

140 m 

320 m 

 

1.25 kPa gas meter pressure 
S.A., W.A., some areas N.S.W. 
Maximum run of copper pipe with average number of fittings 

Model 

20 mm 

25 mm 

32 mm 

40 mm 

50 mm 

HW130 

18 m 

85 m 

300 m 

320 m 

HW160 

10 m 

45 m 

160 m 

320 m 

 
 

2.75 kPa gas meter pressure 
N.S.W. some areas, some new areas of Victoria. 
Maximum run of copper pipe with average number of fittings 

Model 

15 mm 

20 mm 

25 mm 

32 mm 

HW130 

12 m 

100 m 

320 +m 

HW160 

8 m 

65 m 

260 m 

320 +m 

 

NO allowance has been made for other appliances connected to the gas main. This information is supplied as an 
indication of the capacities only. Refer to the latest issue of     AG601 for full details. 

7.0  TROUBLESHOOTING 

BOILER WILL NOT LIGHT 
Possible cause 

Remedy 

Automatic ignition system fails 

Check water flow light indicator. 

Pump not running 

Check pump and flow switch 

Pump air locked 

Air bleed system & pump bearing 

Flow switch open 

Check continuity   

Defective gas control 

Shut off gas supply and call for service 

Thermostat turned off 

Turn on 

Set temperature lower than water temperature 

Increase set temperature 

Water too hot-fault condition displayed 

Refer to fault indication table 

High Limit Thermostat open 

Reset  

Insufficient water flow 

Check for too many valves turned off 

BOILER MAKING KNOCKING NOISES 
Possible cause 

Remedy 

Boiler operating after pump has shut off 

Shut off gas supply and call for service 

Heat exchanger scaled 

Shut off gas supply and call for service 

 

If the boiler cannot be made to perform correctly, please contact the Hurlcon Service Office closest to you. 
 
 
 
For 

VICTORIA: 

 

   

 

Phone (03) 9554 2275 

 

NEW SOUTH WALES:   

             Phone (02) 9853 2100 

 

QUEENSLAND:  

 

             Phone (07) 3308 5400 

 

SOUTH AUSTRALIA 

 

             Phone (08) 8152 7600 

 

WESTERN AUSTRALIA 

 

Phone (08) 9350 2600 

 
For all other areas, please contact our Victorian office. 
 

 

Содержание HW130

Страница 1: ...0 Perth 08 9350 2600 Sydney 02 9853 2100 Townsville 07 4750 3100 sales hurlconheating com au Brisbane 07 3308 5400 Adelaide 08 8152 7600 www hurlconheating com au INSTALLATION AND OPERATING INSTRUCTIO...

Страница 2: ...ESSURE VESSEL 9 4 0 COMMISSIONING 9 4 1 STARTING BOILER 9 4 2 TESTING BURNER PRESSURE 9 10 4 3 FLOW SWITCH 10 4 4 GENUS IV 3 BUTTON CONTROLLER 10 5 0 OPERATING INSTRUCTIONS 11 5 1 ENERGY SAVING TIPS 1...

Страница 3: ...en or infirm person without supervision Please ensure that young children are supervised to ensure that they do not play with the appliance 1 1 NOTICE TO INSTALLERS This is a Wall Mounted External Hot...

Страница 4: ...lve 1 Bar pre set Packed weight 50kg 60kg 2 1 STANDARD EQUIPMENT Electronic control including Set and flow temperature display Electronic ignition Safety devices Built in flow switch Built in run on t...

Страница 5: ...t 3 1 SAFETY RULES For your safety read before lighting This appliance is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand BEFORE OPERATING...

Страница 6: ...mechanical air inlet or any other opening into a building with the exception of sub floor ventilation Appliances up to 150 MJ h input 300 Appliances over 150 MJ h but less than 200 MJ h input 500 App...

Страница 7: ...connector from terminal IN 1 on the small heatsaver PC board in the electrical box and make safe This is the middle terminal on the top side See page 16 3 4 1 GAS CONNECTION A BSP FI is provided for g...

Страница 8: ...he correct pipe sizes for the heating system It is important that the pipe sizes are correctly calculated before installation Hurlcon recommend a two pipe system with the pipes sized according to the...

Страница 9: ...d indicate water temperature Pump should start the flow symbol should be displayed Turn controller switch ON After a few seconds the burner should ignite Do not light by any other means If the burner...

Страница 10: ...ry default 90 For floor heat applications the boiler can be selected for 55 max setpoint by a jumper on the PCB See page 16 Hurlcon Genus IV room thermostat If a Hurlcon Genus IV room thermostat is fi...

Страница 11: ...is a danger of freezing water should circulate through your boiler even if the heating is off 5 2 MAINTENANCE It is recommended that the following items are professionally checked at least every six m...

Страница 12: ...event further heating A lock out condition is indicated by the symbols F1 or F2 on the display To reset a lock out condition turn the controller off for five seconds An F2 condition will first require...

Страница 13: ...es Flow indicator on 6 0 GAS CONVERSION 6 1 BURNER CONVERSION 1 Turn off and disconnect gas supply to unit 2 Turn off power supply to pump and heater 3 Remove front access doors 4 Disconnect flexible...

Страница 14: ...TING BOILER WILL NOT LIGHT Possible cause Remedy Automatic ignition system fails Check water flow light indicator Pump not running Check pump and flow switch Pump air locked Air bleed system pump bear...

Страница 15: ...tion the boiler maximum setpoint can be altered from 90 to 55 This should be done prior to start up however if this is done after power has been applied to the boiler un plugging and reconnecting powe...

Страница 16: ...y if the boiler is installed and operated in complete compliance with the installation and operating instructions The warranty shall not apply to any boilers or parts that have been subject to acciden...

Страница 17: ...top mounting bracket at the desired height Mark the fixing hole locations for the bottom mounting bracket with the holes at 820mm centres Securely fix the top and bottom mounting bracket WS0901 WS0902...

Страница 18: ...HW130 HW160 Hot Water Boilers 18...

Страница 19: ...HW130 HW160 Hot Water Boilers 19...

Страница 20: ...e Victoria New South Wales Queensland South Australia Western Australia Gold Coast Townsville Ph 03 9554 2275 Ph 02 9853 2100 Ph 07 3308 5400 Ph 08 8152 7600 Ph 08 9350 2600 Ph 07 5552 2600 Ph 07 4750...

Отзывы: