Flow Meter Body
Flow meters are designed to be
installed
horizontally only
, with the dial facing
up. Not vertically. Analog dial for manual readings
in U.S. are shown in US gallons (Int. customers
the dial reads in Cubic Meters). Units can be
changed in App to gallons or liters.
Adapter
Brass unions included to fit your irrigation system.
Entry Location
Install between the
master valve
and
zone valves. Meter should be installed
10 times pipe diameter before and 5
times after with straight pipe and no
fittings. See example:
Pipe
10x-Before
5x-After
3/4"
7.5"
3.75"
1"
10"
5"
1.5"
15"
7.5"
2"
20"
10"
Cable used
(shielded cable only)
18 gauge - 1000 foot max Length.
Shielded
direct burial cable must be used.
Cable should
consist of two dedicated wires and must not be in
the same conduit, cable bundle or trench as the
solenoid wires. DO NOT share common wire.
Shielded cable is commonly available, here are
some manufacturers (Paige
[12]
& Regency
[13]
For
additional information on avoiding electrical
interference, see below:
Flow meter body
Arrow indicates direction of flow.
Wire Connection
controller.
Log in to your account
Enter your login
[15]
information.
Create your flow sensor
App will show options for all HC meters.
Creating Alerts
See link here
[16]
Reading Meter
See link here
[17]
Testing Meter
See link here
[18]
Copyright 2020 Hunter Industries. All Rights Reserved.
34