background image

3

to the panel at the Base connection on the front of the panel as shown 

in Figure 2. The connection for the tap water to the base of the sample 

via the volume change device requires a ¼ inch to 1/8 inch push-to-

connect adapter to allow the attachment of ¼ inch tubing from the 

panel to the 1/8 inch OD tubing which connects to the volume change 

device. This adapter is supplied with the panel. The Automatic Volume 

Change device also connects to the solenoid valve on the triaxial cell as 

shown in Figure 4. The solenoid valve has a compression fitting.

TRIAXIAL CELL CONNECTION

The triaxial cell has compression fittings on the front as shown in Figure 

4. The Cell connection on the triaxial cell (valve V3 in Figure 4) connects 

to the Cell port connection on the front of the panel (see Figure 2).

DE-AIRING TANK CONNECTION

The de-airing tank has connections for the tap water in, de-aerated 

water out, and air/vacuum lines. These lines connect to the back side of 

the panel at the corresponding push-to-connect fittings located adjacent 

to the input connections for compressed air, vacuum, tap water, and 

drain.

ELECTRICAL CONNECTION

There are no electrical connections required on the HM-4155 

Distribution Panel. 

OPERATION

After making all of the necessary connections, check to make sure all 

of the valves on the front of the panel are set to the off position. Also, 

loosen the jam nuts on the regulators as shown in Figure 3.

AIR PRESSURE ADJUSTMENT

There are two separate regulators on the panel. The main regulator, 

located below the gauge labeled SYSTEM AIR PRESSURE, controls the 

supply of air for all air connections on the front of the panel and also for 

the auxiliary regulator. The auxiliary regulator labeled AUXILIARY AIR 

PRESSURE in the upper right corner controls the air pressure up to 10 

psi for the auxiliary air pressure port and for the de-airing tank to assist 

in draining the de-airing tank. This regulator has a locking knob which 

must be pulled out to adjust the pressure or pushed in to lock it into 

position (Figure 5).

AIR/WATER CONTROL VALVES

There are several control valves on the panel for on/off operation of  

the air and water control. There are two valves under the De-Airing 

Tank heading (Figure 6). These valves control flow of water to and from 

the de-airing tank and air or vacuum to the tank. The water flow valve 

either allows tap water to fill the tank or allows the tank to be drained 

for cleaning and maintenance. The other valve is for the application of 

Содержание HM-4154

Страница 1: ...product manual HM 4155_MAN_0812 HM 4155 HM 4154 3 Cell Auto Control Panel 1 Cell Auto Control Panel ...

Страница 2: ...a simple free standing bench mounted system which requires no fixed mounting PANEL MOUNTING A pair of supporting feet is supplied with the panel so that it can be bench mounted and remain stable Screws nuts and washers for the support feet are supplied so that the support feet can be attached as shown in Figure 1 AIR WATER CONNECTIONS All connections will require either 1 4 inch OD or 1 8 inch OD ...

Страница 3: ...onnect adapter to allow the attachment of inch tubing from the panel to the 1 8 inch OD tubing which connects to the volume change device This adapter is supplied with the panel BLADDER CYLINDER CONNECTION The HM 4151A Air Water Bladder Cylinders have push to connect style fittings at the bottom of the assembly These fittings use the inch OD tubing and attach the by the same method as the fittings...

Страница 4: ...electrical connections required on the HM 4155 Distribution Panel OPERATION After making all of the necessary connections check to make sure all of the valves on the front of the panel are set to the off position Also loosen the jam nuts on the regulators as shown in Figure 3 AIR PRESSURE ADJUSTMENT There are two separate regulators on the panel The main regulator located below the gauge labeled S...

Страница 5: ...o the corresponding bladder cylinder and the other controls the flow of de aerated water to the Auto Volume Change and to the other bladder cylinder in the apparatus Figure 8 When the valve for the cell is in the FILL position water flows to the cell and bladder cylinder at the same time When the valve labeled PWP is in the FILL position de aerated water flows to the sample base through the Automa...

Страница 6: ...pressure If so the fluids will spray out at high velocity If the filter becomes dirty and clogged open the drain plug as described above to relieve pressure Remove the bowl by rotating the bowl counterclockwise to unscrew it from the filter body Be careful not to lose or damage the o ring that seals the bowl to the body of the filter Next unscrew the filter support by turning it counterclockwise u...

Страница 7: ...99B TRIAXIAL CELL HM 4170 PWP HM 3000 DIGITAL MASTER LOADER HM 2450A AUTOMATIC PRESSURE CONTROLLER HM 2315 AUTOMATIC VOLUME CHANGE DEVICE HM 4151A BLADDER AIR WATER CYLINDER HM 2310 10 DISPLACEMENT TRANSDUCER HUMBOLDT MFG CO FULLY AUTOMATED 3 TRIAXIAL CELL SYSTEM COMPRESSED AIR VACUUM TAP WATER DRAIN TO BASE VALVE TO CELL VALVE FIGURE 2 ...

Страница 8: ...R PRESSURE PUSH DOWN TO RELEASE CONNECTOR FIGURE 3 Figure 3 Figure 4 Triaxial Cell BASE WATER CONNECTION DISTRIBUTION PANEL SOLENOID VALVE PORE WATER PRESSURE TRANSDUCER V1 V2 V3 V4 V5 VENT VALVE LEVER FIGURE 4 AUTO VOLUME CHANGE CONNECTION ...

Страница 9: ...SE PRESSURE TO THE DE AIRING TANK TO THE AUXILIARY AIR CONNECTOR FIGURE 5 REGULATING AUXILIARY AIR PRESSURE FIGURE 6 DE AIRING TANK CONTROL VALVES DE AIRED WATER FILL DRAIN OFF VACUUM PRESSURE TURN KNOB LEFT TO FILL DE AIRING TANK WITH TAP WATER OR TURN KNOB RIGHT TO DRAIN DE AIRING TANK TURN KNOB LEFT TO APPLY VACUUM TO DE AIRING TANK OR TURN KNOB RIGHT TO APPLY PRESSURE TO ASSIST DRAINING OF DE ...

Страница 10: ...URE 7 AIR PRESSURE CONTROL VALVE WATER CONNECTION CELL BLADDER A FILL DRAIN BASE BLADDER B FILL CELL PWP FIGURE 8 CELL AND SAMPLE BASE WATER CONTROLS TURN KNOB UP TO FILL CELL AND BLADDER CYLINDER A WITH TAP WATER TURN KNOB DOWN TO DRAIN CELL AND BLADDER TURN KNOB DOWN TO FILL SAMPLE AND BLADDER CYLINDER B WITH DE AERATED WATER 8 ...

Страница 11: ...nstream adjust drip rate accordingly Consult oil delivery conversion chart see below Generally one drop per minute downstream for every 10 15 SCFM flow is satisfactory 25 drops per minute equals one ounce per hour volume of oil passing through the sight dome NOTE This is a constant density type lubricator which delivers a constant ratio of oil to air flow Therefore if air flow increases or decreas...

Страница 12: ...r parts of such product for the warranty of this product please refer to Humboldt Mfg Co catalog on Terms and Conditions of Sale The purchaser is responsible for the transportation charges Humboldt Mfg Co shall not be responsible under this warranty if the goods have been improperly maintained installed operated or the goods have been altered or modified so as to adversely affect the operation use...

Отзывы: