Configuration manual EGS(H)41
19
5
Parameters 2
On this page the settings are made that define the safety-relevant characteristics of theEGS(H)41.
5.1
Broken wire detection
Broken wire detection is available for the switching outputs S1 and S2. Detection is triggered as soon
as the internal load current monitoring measures less than 5 mA when a switch is closed.
PLEASE NOTE!
This detection cannot function if there are opened contacts in the safety circuit in series to
the switch output.
5.2
Delayed overcurrent switch-off
A switching load with high initial current requirements can trigger an undesired over-current switch-off.
It is possible to delay this overcurrent detection 1 ms, 2 ms or 5 ms.
5.3
Identification and password
In the middle section, you can give the device any user device name. This makes it easier to allocate
EGS(H) 41 to its place of installation (e.g. “hoist 22”). The device name is limited to 12 characters.
Furthermore, in the second line of the middle section, you can define a new password for access to
the configuration. With this password, only an authorized group of users will be able to change the
configuration. To verify your authorization, enter the current password in the left box and the new
password in the right box.
Press “change” to activate the new password in the device.
The password must be created from the alphanumeric characters a-z, A-Z and 1-9. The maximum
length of the password is limited to 12 characters.