background image

Electrical equipment should only be installed, operated, serviced and maintained by qualified personnel. 

______________

Hubbell Wiring Devices

No responsibility is assumed by Hubbell for any consequences arising out of the use of this material. 

__

1-800-729-3406 | www.Hubbell-Wiring.com

7

Terminals, Wire Size, and 
Installation Torque

Terminals are provided for phase (line), neutral, and equipment ground 
connections. The terminals accept a range of 10 AWG to 2 AWG copper wire for 
the offer without internal switch for phase, neutral and ground connectors and  
10 AWG to 3/0 AWG copper wire for the switch offer for phase connectors. 
Torque connections to the following values:

Table

 

2:

Terminal Torque

Power Connection

Torque

AØ, BØ, CØ and N

40 lb-in. (4 N•m)

Ground
Switch

50 lb-in. (5 N•m)

Branch Circuit Overcurrent 
Protection

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Use conductors rated for the Overcurrent Protection Device (OCPD) per 

applicable codes.

• Use conductors rated for the application per applicable codes.

Failure to follow these instructions will result in death or serious injury.

UL 1449 Type 1 SPDs have been designed and approved for line side 
applications prior to the main service disconnect without supplemental 
overcurrent protection. Type 1 SPDs may also be installed on the load side of 
the main Overcurrent Protection Device (OCPD).

Location of Surge Protective 
Device (SPD)

Locate the SPD as close as possible to the circuit being addressed to minimize 
the wire length and optimize SPD performance. Avoid long wire runs so that the 
device will perform as intended. To reduce wire impedance from surge currents, 
the phase, neutral, and ground conductors must be routed within the same 
conduit and tightly bundled or twisted together to optimize device performance. 
Avoid sharp bends in the conductors. See Figure

 

2.

Figure

 

2:

Surge Protective Device Wiring Practice

To load(s)

Phases

Neutral 

(if applicable)

Ground

Ground bus

Neutral bus

SPD

Phase A

Phase B

Phase C

Neutral

(if applicable)

Ground

Interconnect wiring
 – Minimize length 

 – Avoid sharp bends

Panel

DANGER

SpikeShield

® 

Modular Panel Surge Protective Device (SPD)

ELECTRICAL

Содержание Spikeshield HBL10P120C

Страница 1: ...BL5P160B HBL5P320B HBL5P320B HBL5P320DB HBL6P120C HBL6P160B HBL6P160DB HBL6P320B HBL6P320DB HBL8P120C HBL8P160B HBL8P160DB HBL8P320B HBL8P320DB HBL9P120C HBL9P160B HBL9P160DB HBL9P320B HBL9P320DB HBL1...

Страница 2: ...ure Considerations 10 Removing and Reconnecting the RJ45 Diagnostic Cables 10 Optional Flush Mounting 10 Wiring 10 Dimension and Weights EMA Series 12 Wiring Diagrams Without Integral Switch 13 Wiring...

Страница 3: ...to signal an alarm state to the central supervisory system for unmanned inaccessible or critical installations Use multiple SPDs to achieve redundancy for critical applications Failure to follow thes...

Страница 4: ...tive to maximize the SPD s surge protective device s effectiveness and performance Read the entire instruction bulletin before beginning the installation These instructions are not intended to replace...

Страница 5: ...interconnecting wiring length For every foot of wire length approximately 160 Volts 6 kV 3 kA 8 20 microsecond is added to the suppressed voltage The Voltage Protection Rating VPR is located on the de...

Страница 6: ...DB 320 kA HBL8P320B 320 kA HBL8P320DB 480 V 3 phase 3 wire ground Delta 4 4 480 V Delta series also applies to the following voltages 480Y 277V HRG 120 kA HBL9P120C 160 kA HBL9P160B 160 kA HBL9P160DB...

Страница 7: ...d for the application per applicable codes Failure to follow these instructions will result in death or serious injury UL 1449 Type 1 SPDs have been designed and approved for line side applications pr...

Страница 8: ...ents connected from phase to ground It is critical that there be a robust and effective connection to the building grounding structure The grounding connection must utilize an equipment grounding cond...

Страница 9: ...d power systems are inherently unstable and can produce excessively high line to ground voltages during certain fault conditions During these fault conditions any electrical equipment including an SPD...

Страница 10: ...derations Removing and Reconnecting the RJ45 Diagnostic Cables The diagnostic cables are marked with matching phase connections If any of the cables are removed reconnect the cables as marked Optional...

Страница 11: ...ns Note The neutral connection is not present on three phase three wire WYE solidly ground or two wire single phase mid point ground power systems For these systems bond the neutral and ground lugs to...

Страница 12: ...x 20 in NEMA 1 Enclosures with Integral Switch Approximate Weight 27 lbs 12 2 kg Figure 5 11 x 22 in NEMA 1 Enclosures for 320 kA and 480 kA units with or without Integral Switch Approximate Weight 37...

Страница 13: ...conductor is not present on two wire grounded power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire NEUTRAL GROUND PHASE C N A C See Note PHASE A...

Страница 14: ...power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire PHASE A PHASE B NEUTRAL GROUND PHASE C A B N C See Note Customer Connections 120 240 kA Custo...

Страница 15: ...eutral conductor is not present on three wire grounded power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire PHASE C PHASE A PHASE B See Note NEUTR...

Страница 16: ...t present on two wire grounded power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire SPD NEUTRAL GROUND PHASE C N A C See Note PHASE A Customer Con...

Страница 17: ...present on three wire grounded power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire PHASE C PHASE A PHASE B NEUTRAL GROUND N See Note A B C Custom...

Страница 18: ...ustomer Connections 120 240 kA Ground Phase A Neutral Phase C Phase B Phase A Phase C Phase B Ground Neutral SURGE PROTECTIVE DEVICE Push to Test OK Replace Module Surge Counter Audible Alarm A B C 82...

Страница 19: ...ounded phase Customer Connections 320 480 kA Customer Connections 100 240 kA Ground Phases A B C Phase A Phase B Phase C Ground Customer Connections 320 480 kA with Integral Switch Customer Connection...

Страница 20: ...er Connections 320 480 kA with Integral Switch Customer Connections 100 240 kA with Integral Switch Ground Phase A Phase C Phase B Phase A Phase C Phase B Ground SURGE PROTECTIVE DEVICE Push to Test O...

Страница 21: ...utton will complete the test the red LED will turn green and the alarm will shut off If an inoperable condition occurs on any phase the audible alarm sounds and the corresponding phase LED on the diag...

Страница 22: ...wer and press the small switch located inside the unit on the underside of the diagnostic circuit board near the RJ45 connectors also refer to Figure 17 This will reset the counter to zero Figure 15 T...

Страница 23: ...alarm condition exists See Table 4 These contacts can be used for remote indication of the SPD s operating status to a computer interface board or emergency management system Also these contacts are...

Страница 24: ...inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effect...

Страница 25: ...oltage correct Are all module LEDs on Possible diagnostic display board failure Contact Hubbell at 1 800 729 3406 for troubleshooting NO YES YES YES NO YES YES NO Check the power utility feed and veri...

Отзывы: