Hubbell Spikeshield HBL10P120C Скачать руководство пользователя страница 21

Electrical equipment should only be installed, operated, serviced and maintained by qualified personnel. 

______________

Hubbell Wiring Devices

No responsibility is assumed by Hubbell for any consequences arising out of the use of this material. 

__

1-800-729-3406 | www.Hubbell-Wiring.com

21

Operation

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Apply appropriate personal protective equipment (PPE) and follow safe 

electrical work practices. See NFPA 70E.

• This equipment must only be installed and serviced by qualified electrical 

personnel.

• Turn off all power supplying this equipment before working on or inside 

equipment.

• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this 

equipment.

• This equipment must be effectively grounded per all applicable codes. Use 

an equipment-grounding conductor to connect this equipment to the power 
system ground.

Failure to follow these instructions will result in death or serious injury.

LED Status Indicators

The SPD diagnostic display panel shows the status of each SpikeShield module 
with diagnostically controlled green/red LEDs (see Figure 16). If a unit is 
operating correctly, all of the phase LEDs will be illuminated green. To test the 
integrity of the diagnostics for each phase, push the button below the phase 
LEDs on the diagnostic display panel. The green LED will turn red and the alarm 
will sound, if the alarm is enabled. Releasing the test button will complete the 
test; the red LED will turn green and the alarm will shut off.

If an inoperable condition occurs on any phase, the audible alarm sounds and 
the corresponding phase LED on the diagnostic display panel is illuminated red. 
This indicates that the device needs service by qualified electrical personnel. 
The audible alarm can be silenced, until a qualified person is able to evaluate 
and service the SPD, by pressing the alarm enable/disable button. The alarm 
will silence and the green alarm LED will not be lit. The red phase LED will 
continue to be illuminated until the inoperative condition had been cleared.

On the SPD module (see Figure 14), if either LED is not lit, the module should be 
replaced. If both green LEDs are not lit and the diagnostic display panel has 
power, then power has been lost to that phase or the module should be replaced 
(refer to Table 1 on page 6). Refer to the final equipment instruction bulletin for 
SPD module disconnection and access instructions.

When power is applied to the SPD and one or more of the diagnostic display 
panel LEDs are red, and one or more module LEDs are out, the appropriate 
module should be replaced. Refer to “Maintenance and Troubleshooting” on 
page 25 for proper troubleshooting.

Figure

 

14:

SpikeShield LEDs

Left green LED lit: 

L-G suppression 

is operating.

Left green LED not lit: 

Loss of surge suppression 

from L-G.

Right green LED not lit:
Loss of surge suppression from
L-N for MA(1, 3, 4, or 8)IMA_
L-L for

 

Right green LED lit:
Suppression is operating
L-N for MA(1, 3, 4, or 8)IMA_
L-L for  MA(5, 6, or 9)IMA_ (Delta/HRG)

MA(5, 6, or 9)IMA_ (Delta/HRG)

DANGER

SpikeShield

® 

Modular Panel Surge Protective Device (SPD)

OPERATION

Содержание Spikeshield HBL10P120C

Страница 1: ...BL5P160B HBL5P320B HBL5P320B HBL5P320DB HBL6P120C HBL6P160B HBL6P160DB HBL6P320B HBL6P320DB HBL8P120C HBL8P160B HBL8P160DB HBL8P320B HBL8P320DB HBL9P120C HBL9P160B HBL9P160DB HBL9P320B HBL9P320DB HBL1...

Страница 2: ...ure Considerations 10 Removing and Reconnecting the RJ45 Diagnostic Cables 10 Optional Flush Mounting 10 Wiring 10 Dimension and Weights EMA Series 12 Wiring Diagrams Without Integral Switch 13 Wiring...

Страница 3: ...to signal an alarm state to the central supervisory system for unmanned inaccessible or critical installations Use multiple SPDs to achieve redundancy for critical applications Failure to follow thes...

Страница 4: ...tive to maximize the SPD s surge protective device s effectiveness and performance Read the entire instruction bulletin before beginning the installation These instructions are not intended to replace...

Страница 5: ...interconnecting wiring length For every foot of wire length approximately 160 Volts 6 kV 3 kA 8 20 microsecond is added to the suppressed voltage The Voltage Protection Rating VPR is located on the de...

Страница 6: ...DB 320 kA HBL8P320B 320 kA HBL8P320DB 480 V 3 phase 3 wire ground Delta 4 4 480 V Delta series also applies to the following voltages 480Y 277V HRG 120 kA HBL9P120C 160 kA HBL9P160B 160 kA HBL9P160DB...

Страница 7: ...d for the application per applicable codes Failure to follow these instructions will result in death or serious injury UL 1449 Type 1 SPDs have been designed and approved for line side applications pr...

Страница 8: ...ents connected from phase to ground It is critical that there be a robust and effective connection to the building grounding structure The grounding connection must utilize an equipment grounding cond...

Страница 9: ...d power systems are inherently unstable and can produce excessively high line to ground voltages during certain fault conditions During these fault conditions any electrical equipment including an SPD...

Страница 10: ...derations Removing and Reconnecting the RJ45 Diagnostic Cables The diagnostic cables are marked with matching phase connections If any of the cables are removed reconnect the cables as marked Optional...

Страница 11: ...ns Note The neutral connection is not present on three phase three wire WYE solidly ground or two wire single phase mid point ground power systems For these systems bond the neutral and ground lugs to...

Страница 12: ...x 20 in NEMA 1 Enclosures with Integral Switch Approximate Weight 27 lbs 12 2 kg Figure 5 11 x 22 in NEMA 1 Enclosures for 320 kA and 480 kA units with or without Integral Switch Approximate Weight 37...

Страница 13: ...conductor is not present on two wire grounded power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire NEUTRAL GROUND PHASE C N A C See Note PHASE A...

Страница 14: ...power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire PHASE A PHASE B NEUTRAL GROUND PHASE C A B N C See Note Customer Connections 120 240 kA Custo...

Страница 15: ...eutral conductor is not present on three wire grounded power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire PHASE C PHASE A PHASE B See Note NEUTR...

Страница 16: ...t present on two wire grounded power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire SPD NEUTRAL GROUND PHASE C N A C See Note PHASE A Customer Con...

Страница 17: ...present on three wire grounded power systems For these systems bond the neutral and ground lugs together inside the SPD using 10 AWG wire PHASE C PHASE A PHASE B NEUTRAL GROUND N See Note A B C Custom...

Страница 18: ...ustomer Connections 120 240 kA Ground Phase A Neutral Phase C Phase B Phase A Phase C Phase B Ground Neutral SURGE PROTECTIVE DEVICE Push to Test OK Replace Module Surge Counter Audible Alarm A B C 82...

Страница 19: ...ounded phase Customer Connections 320 480 kA Customer Connections 100 240 kA Ground Phases A B C Phase A Phase B Phase C Ground Customer Connections 320 480 kA with Integral Switch Customer Connection...

Страница 20: ...er Connections 320 480 kA with Integral Switch Customer Connections 100 240 kA with Integral Switch Ground Phase A Phase C Phase B Phase A Phase C Phase B Ground SURGE PROTECTIVE DEVICE Push to Test O...

Страница 21: ...utton will complete the test the red LED will turn green and the alarm will shut off If an inoperable condition occurs on any phase the audible alarm sounds and the corresponding phase LED on the diag...

Страница 22: ...wer and press the small switch located inside the unit on the underside of the diagnostic circuit board near the RJ45 connectors also refer to Figure 17 This will reset the counter to zero Figure 15 T...

Страница 23: ...alarm condition exists See Table 4 These contacts can be used for remote indication of the SPD s operating status to a computer interface board or emergency management system Also these contacts are...

Страница 24: ...inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effect...

Страница 25: ...oltage correct Are all module LEDs on Possible diagnostic display board failure Contact Hubbell at 1 800 729 3406 for troubleshooting NO YES YES YES NO YES YES NO Check the power utility feed and veri...

Отзывы: