background image

Page 2 of 3

3940 Dr. Martin Luther King Drive

St. Louis, MO 63113
KIL00921465 FORM NO. K1465 06/15 ERO-8-029-15 

For Class I, Division 2, Groups A, B, C & D

Class II, Division 1, Groups E, F & G; Class III. 

Type  3  and  4.  IP66.  Operating  Temperature  Range 

-50°C +60°C

 

1. 

Back Nut

2.  Middle Nut

3.  Grounding Spring (Captive in the Middle Nut)

4.  Armor Stop

5.  Elbow

6.  Locking Collar

7.  Potting Chamber

8.  Entry Component

9.  O-Ring (Captive in Entry Component)

ASSEMBLY INSTRUCTIONS

 

STEP A 

(Refer to Figure A on left)

    Strip  cable  to  suit  equipment  as  shown  above,   

exposing  metal  armor  sheath  (I)  and  insulated 

cores (II).

= 3/4” (19mm) for ½” size glands

I

 = 13/16” (21mm) for ¾” size glands

= 1” (25mm) for 1” size glands

= 1-1/4” (32mm) for1-¼” size glands

II

 to suit equipment

 

STEP B 

(Refer to Figure B on left)

    Push the cable through the back nut (1), middle 

nut (2), and grounding spring (3). Locate the armor 

stop (4) at the end of the armor as shown below. If 

the conductors are too large to fit through the armor 

stop (4) it can be removed from the assembly. The 

elbow component (5) has a built in armor stop for 

larger  cables.  Feed  the  wires  through  the  elbow 

and tighten the middle nut (2) and backnut (1) to 

the torque shown in Table A (Approximately hand 

tight  +  1  turn). This  will  compress  the  grounding 

spring (3) to grip the armor for grounding.

Figure A

Figure B