14
Model
kW
Volts /
Phase
Amps
Min.
Breaker
Size
Wire
Size
(Qty.)
Conduit
Size
Wiring
Diagram
Element
Amp
Draw
JTX027-3T6
27
600 / 3
26.0
30
8
¾"
5
26.0
JTX030-6T3
30
380 / 3
45.6
50
8
¾"
9
13.2
JTX031-6RS
31
208 / 1
149.0
175*
2/0
1 ½"
6
25.3
JTX031-6R
31
208 / 3
86.0
90
3
1"
7
25.3
JTX031-6T7
31
415 / 3
43.1
50
8
¾"
9
12.6
JTX033-6S
33
240 / 1
137.5
150*
1/0
1 ¼"
6
22.9
JTX033-6T
33
240 / 3
79.4
90
4
1"
7
22.9
JTX036-6RS
36
208 / 1
173.1
200*
3(2)
1 ½"
6
28.9
JTX036-6R
36
208 / 3
99.9
110
2
1"
8
28.9
JTX036-6T3
36
380 / 3
54.7
60
6
¾"
9
15.7
JTX036-6T7
36
415 / 3
50.1
60
6
¾"
9
14.4
JTX036-6T4
36
480 / 3
43.3
50
8
¾"
9
12.5
JTX040-6RS
40
208 / 1
192.3
225*
2(2)
2"
6
32.5
JTX040-6R
40
208 / 3
111.0
125
1
2"
8
32.5
JTX040-6T3
40
380 / 3
60.8
70
6
¾"
9
17.7
JTX040-6T7
40
415 / 3
55.6
60
6
¾"
9
16.2
JTX042-6S
42
240 / 1
175.0
200*
3(2)
1 ½"
6
29.2
JTX042-6T
42
240 / 3
101.0
110
2
1"
8
29.2
JTX042-6T4
42
480 / 3
50.5
60
6
¾"
9
14.6
JTX042-6T6
42
600 / 3
40.4
45
8
¾"
10
40.4
JTX048-6RS
48
208 / 1
230.8
250*
1(2)
2"
6
38.5
JTX048-6R
48
208 / 3
133.2
150*
1/0
1 ¼"
12
38.5
JTX048-6S
48
240 / 1
200.0
225*
2(2)
2"
6
33.3
JTX048-6T
48
240 / 3
115.5
125
1
2"
8
33.3
JTX048-6T7
48
415 / 3
66.8
80
4
1"
9
19.3
JTX048-6T4
48
480 / 3
57.7
70
6
¾"
9
16.7
JTX048-6T6
48
600 / 3
46.2
50
8
¾"
10
46.2
JTX050-6T3
50
380 / 3
76.0
80
4
1"
9
22.2
JTX054-6S
54
240 / 1
225.0
250*
1(2)
2"
6
37.5
JTX054-6T
54
240 / 3
129.9
150*
1/0
1 ¼"
12
37.5
JTX054-6T4
54
480 / 3
65.0
70
4
1"
9
18.8
JTX054-6T6
54
600 / 3
52.0
60
6
¾"
10
52.0
□
Tankless booster heaters are considered a non-continuous load.
□
If a multiple feed installation is used, it is acceptable to install up to two conductors in
one line side port. Additionally, when a power distribution block is supplied,
additional conductors may be installed in an open load side port of the power
distribution block.
□
Wiring sizing listed is for 75°C THHN. 60°C or 90°C wire may be used. Refer to
NEC table 310.16 for sizing.
□
Conductors should be sized to maintain a voltage drop of less than 3% under load.
□
Electrical specifications for the High Flow (JHX) models are the same as listed for the
Low Flow (JTX) models.
□
The Hubbell Model JTX is designed for use with conveyor and flight type dish
machines. This product is not intended for use with door style dish machines.
Содержание JHX
Страница 10: ...10...
Страница 16: ...16 Wiring Diagram 1 Wiring Diagram 2...
Страница 17: ...17 Wiring Diagram 3 Wiring Diagram 4...
Страница 20: ...20 Wiring Diagram 8...
Страница 22: ...22 Wiring Diagram 10...
Страница 30: ...30 Initial Evaluation...
Страница 43: ...43 NOTES...
Страница 44: ...44 P O BOX 288 STRATFORD CT 06615 0288 PHONE 203 378 2659 FAX 203 378 3593 INTERNET http www hubbellheaters com...