TROUBLE SHOOTING
•
“EXIT” legend does not illuminate
• Check wiring connections.
•
Emergency circuit does not work
• Batteries are shipped uncharged and disconnected. Connect power pack leads and charge before testing.
• Make sure charger board is properly seated.
• Check wiring connections.
TESTING
Signs should be tested and maintained in accordance with National Electrical Code and NFPA 101 Life Safety Code requirements. It is recommended that
emergency exit signs be tested for 30 seconds once a month and for 90 minutes once a year.
REPLACING A BATTERY PACK
De-energize the AC power supply to the exit sign; remove the clear cover. Remove the white trim plate and the exit sign face. Disconnect the 2-pin battery
pack connector from the charger board. Remove the battery pack from the compartment. Install a new battery pack with the correct part number into the
compartment, and plug in the 2-pin connector to the charger board. Reinstall the exit sign face, white trim plate and secure the clear cover. Energize AC power
to the exit sign. Allow the new battery pack to fully charge, and press the “TEST” button to verify operation.
RECYCLING INFORMATION
All thermoplastic parts are recyclable. All cartons contain recycled materials. Please recycle responsibly.
NOTICE:
Emergency model exit signs contain rechargeable nickel-cadmium batteries which must be recycled or disposed of properly.
LN4X Series
LED Exit Sign Listed For Damp And Wet Locations
AC Non-Emergency Models Are UL Type 4X Rated
Installation, Operation and Maintainance Instructions
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com
Copyright
©
Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A.
93029236A
6/10
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Do not let power supply cords touch hot surfaces.
2. Do not mount near gas or electric heaters.
3. Equipment should be mounted in locations and at heights where it will not readily be subject to tampering
by unauthorized personnel.
4. The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.
5. Do not use this equipment for other than its intended purpose.
6. Servicing of this equipment should be performed by qualified service personnel.
7. Test cycling: the Life Safety Code (NFPA 101) requires testing of emergency exit signs once a month for a
minimum of 30 seconds and once a year for a minimum of 90 minutes.
INSTALLER:
•SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING
–
This product contains chemicals known to the State of California to cause cancer, birth defects and/or other
reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.
93033371
OPERATION
“AC ON” LED is iluminated when AC power is present.
NOTE: All models are supplied with an AC Lockout circuit, which prevents the “EXIT” legend from illuminating when the battery is connected and no AC power
is present.
NOTE: All models are supplied with a Low Voltage Disconnect circuit, which prevents damage to the battery from deep discharge during prolonged
emergency operation.
NOTE: Batteries are often shipped in a discharged state – this is normal. The battery will require charging. Allow several hours of charge before testing the unit.
Models With SPECTRON® Self-Testing/Self-Diagnostic Circuitry
Models equipped with the Spectron self-testing/self-diagnostic electronics system provide:
■
Visual indication of AC power status
■
Visual indication of self-diagnostic test cycle
—Visual indication of any unit malfunctions including—
■
Battery fault
■
Transfer fault
■
Charger fault
■
Emergency
Lamp fault
Spectron equipped units also include:
Brownout protection: unit will automatically transfer to emergency operation upon detection of low AC power (approximately 80% of nominal line).
Time Delay Retransfer: upon return of normal AC power, unit will remain in the emergency mode for an additional 15 minutes to allow AC power to stabilize.
LED Status Indicator
A bicolor LED (green/red) is provided on the control panel of all models
equipped with the Spectron option.
Red Status Indicator Code
Description
One blink ON/pause
Battery not connected
Two blinks ON/pause
Battery fault
Three blinks ON/pause
Charger fault
Four blinks ON/pause
Transfer circuit fault
Five blinks ON/pause
Emergency Lamp fault
Automatic Tests
The unit will automatically initiate a self-test/self-diag-
nostic cycle based on the following table:
Testing Period
Duration of Test
Once a month
1 minute
Once every 6 months
Alternating:
30 minutes or 60 minutes
Manual Tests
Using the unit test switch, users can initiate different
duration test cycles based on the following table:
Initiating Action
Test Cycle
Press test switch once
1 minute
Press test switch twice
90 minutes
Pressing the test switch at any time after a test cycle has
begun cancels the remainder of the test and returns the
unit to normal operation.
Red Service Alert Indicator
Under normal operating conditions, the red Service Alert Indicator will remain “off”.
In the event the Spectron controller detects a malfunction, the red Service Alert
Indicator will blink at a 1 Hz. rate, based on the following table:
Green Operating Status Indicator
The green Operating Status Indicator serves as both an AC power and a self-test
indicator. During normal operation, the green Operating Status Indicator will be
illuminated, indicating the presence of AC power. During all automatic or manual
self-test cycles, the green Operating Status Indicator will blink at a 1 Hz. rate.
MAINTENANCE