background image

Functional Description 

If occupation is detected by the permanently active PIR sensor, 

a radio telegram indicating the occupied status will transmit 

immediately. A motion transmission interval timer starts to run 

with a variable timer length varying between 60 and 300 sec-

onds, depending on the light level.  No radio telegrams will be 

sent out until the timer expires.
After the timer has expired, the unit will transmit again if occu-

pancy was detected during the timer interval period. If occu-

pancy was not detected, the unit will transmit a heartbeat signal 

- sending the unoccupied heartbeat status message every 2 - 11 

minutes (depending on the light level).

Planning 

Take a moment to plan for the sensor’s successful operation and 

optimal communication with other system components.
Remove the sensor from its packaging and place it under a 

bright light to provide the required startup charge. Optionally, 

to ensure the sensor energy storage is fully charged, insert a 

CR2032 battery for 5 minutes while in a well-lit location.

 

Ensure the location provides consistent and adequate light

 

Install with the appropriate lens for the required coverage

 

Locate the sensor between 6 and 8 ft (1.8 to 2.4 m) high with 

an unobstructed view of the space

 

For wide angle coverage, locate the sensor where traf

fi

 c 

moves across the detection pattern, not in and out

 

Consider the area’s traf

fi

 c patterns and principal use, for 

example, walking, lounging or sleeping

 

Provide a minimum clearance of 4 ft. (1.2 m) away from heat 

sources, light bulbs, forced air, or ventilation systems

 

Consider the construction materials (such as metal) in the 

space and obstacles that may interfere with RF signals

Sensor Range

A single occupancy sensor provides suf

fi

 cient coverage for most 

applications. For some applications, multiple sensors may be 

required to provide complete coverage.

Wide Angle Coverage

0

33 ft (10 m)

16 ft (5 m)

16 ft (5 m)

Top View

6.8 ft

(2.1 m)

6 ft

15 ft 

25 ft

50 ft 

Side View

33 ft (10 m)

Long Range Coverage

16 ft

0

16 ft

8 ft

8 ft

Top View

27°

77°

21.5°

14°

6.5°

center line

Side View

6.8 ft

(2.1 m)

3 ft

(1 m)

7 ft

(2.2 m)

10 ft

(3 m)

35 ft

(10.7 m)

60 ft

(18.3 m)

100 ft

(30.5 m)

Installing

The mounting plate can be installed 

fl

 ush to the wall or angled 

in a corner.
NOTE: It is often easier to link the sensor before it is mounted 

on the wall. Refer to the Linking section.
1.  Remove the mounting plate from the sensor assembly by 

pressing the release tab located on the top of the sensor.

2.  Decide which of the two installation options is appropriate:

A.  Flush to the Wall

i.  Orient the mounting plate 

using the pencil marks. 

Mark the two mounting 

screw drill points.

ii.  Drill two holes with a 3/16” 

bit and insert wall anchors.

iii. Insert the 

fi

 rst screw 

loosely and level the mounting plate.

iv.  Insert the 2nd screw then hand-tighten the 1st screw.

B.  Angled in a Corner

i.  Orient the mounting plate 

using the pencil marks.

ii.  Carefully drill through two of

the four blind holes on the 

angled sides of the mounting 

plate (one on each side).

iii.  Mark the two mounting screw

drill points and drill two pilot holes with a 3/16” 

drill bit and insert the wall anchors.

iv.  Insert the two screws and hand-tighten them.

3.  Fit the sensor into the groove at the bottom of the mounting 

plate and close the top.

p

p

estimated time: 20 minutes

Occupancy Sensor – Wall Mounted • Installation Guide

Page 2

© 2013  Hubbell Building Automation     |     www.hubbell-automation.com

Отзывы: