background image

6

Soft key

Description

OFF

Power Off (No operation, 3 minutes automatic shutdown)

Back

Return to the main menu

H.V

Set test voltage: 500V

1000V

2500V

5000V

10000V

Rt

Veiw 15S

30S

60S

600S Insulation value

V. Instrument Using

measured DAR

:

1. Select more than 1 minute length measurement.

2. Select the appropriate voltage and start.

3. The instrument automatically record 15 s and 60 s resistance, and calculate the

absorption than after 60 seconds.

Absorption ratio calculation method: DAR = R60 / R15;

measured PI :

1. Select more than 10 minute length measurement.

2. Select the appropriate voltage and start.

3. The instrument automatically record 15S, 60S and 600S resistance, and calculate the

polarization index after 600 seconds.

Polarization index calculation method : PI= R600/R60;

test connection points for attention

1.

Tested to confirm product safety grounding, try not charged.

2.

Confirm the instrument E end (ground) have been grounded.

3.

The use of G terminal (protection ring) (this machine is of low voltage side of the

screen)

When measuring high insulation resistance, the sample should be in the position a

conductor surface protection between the two measuring end ring, and the conductor

protection ring is connected to the instrument with a test line G side, try to eliminate the

measuring error caused by the surface leakage current, security testing is accurate.

Содержание HZJY-10K-I

Страница 1: ...HZJY 10K I Insulation Resistance Tester Huazheng Electric Manufacturing Baoding Co Ltd...

Страница 2: ...Contents I Safe Use Items 1 II Feature 2 III Specification Parameter 2 IV Introduction Of Instrument 3 V Instrument Using 6 VI Packing List 7...

Страница 3: ...operators in instrument surface operation Please don t charged the connection test line low Low in the measurement or do not touch the circuit being measured immediately after the test may result in...

Страница 4: ...al discharge when testing cables automatic rapid discharge of instruments 2 power supply modes the battery is powered by lithium ion battery and the battery life can reach 4 hours 10000V 100m test res...

Страница 5: ...range 20uF Capacitance testing accuracy 15 0 03uF Capacitor discharge rate from 10000V to 10V 0 5S F Insulation resistance testing range and accuracy T 23 5 C RH 45 75 range accuracy 500V 1000V 2500V...

Страница 6: ...Power Off No operation 3 minutes automatic shutdown H V Set test voltage 500V 1000V 2500V 5000V 10000V TIME SetThe test time 00 30 01 00 10 00 30 00 Switching software keys to a new function or from...

Страница 7: ...1 key the power button until into the contrast adjustment menu 3 Press 1 or 2 keys to adjust contrast until the right 4 Press the 4 key save and exit if you don t need to adjust the press 3 key to ex...

Страница 8: ...oltage and start 3 The instrument automatically record 15S 60S and 600S resistance and calculate the polarization index after 600 seconds Polarization index calculation method PI R600 R60 test connect...

Страница 9: ...7 VI Packing List No Item Qty 1 Main engine 1 2 Power line 1 3 Black test line 1 4 Red test line 1 5 Green test line 1...

Отзывы: