I.Overview

Lightning arrester is an important electrical equipment in power network to protect

power equipment from over-voltage. Normally, the action of the arrester and leakage

current are monitored through the arrester monitor. Due to poor sealing, the monitor may

enter water or moisture during operation, causing internal element corrosion, or other

reasons, the monitor counter cannot operate normally, and the leakage current indication

is not accurate. Therefore, according to

The Regulations

, the arrester monitor should

be checked once a year

The reliability of counter operation is very important for power system. It is an important

parameter to record the number of lightning strikes received by the arrester in normal

operation. It can provide an important basis for the power system workers to inspect the

arresters.

II.Principle

Figure 1 shows the principle wiring diagram of HZJS action counter. Figure 1 (a) is

the basic structure of HZJS-type action register, namely the dual-disc structure.

Figure 1. Schematic wiring of hzjs-type action register

(a)HZJS Type

(b)HZJS-3KV Type

R

1

R

2

-Non-linear resistance

C-Energy storage capacitor

L-Register coil

D

1

~

4

Silicon diode

When the arrester operates, the discharge current flows through the valve sheet R1,

the voltage drop on the valve sheet R2 charges the capacitor C, and then C discharges

Содержание HZJS-3KV

Страница 1: ...HZJS 3KV HV Surge Counter Tester Huazheng Electric Manufacturing Baoding Co Ltd ...

Страница 2: ...and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this instrument If you are satisfied with this instrument please tell your colleagues if you are not satisfied with this instrument please call 0312 6775656 to tell you to serve you at all times Baoding Huazheng ...

Страница 3: ...Contents I Overview 1 II Principle 1 III Technical Parameter 2 IV Inspection Methods And Principles 2 V Operation Method 3 VI Matters Needing Attention 4 VII Packing List 4 ...

Страница 4: ...unter operation is very important for power system It is an important parameter to record the number of lightning strikes received by the arrester in normal operation It can provide an important basis for the power system workers to inspect the arresters II Principle Figure 1 shows the principle wiring diagram of HZJS action counter Figure 1 a is the basic structure of HZJS type action register na...

Страница 5: ... count The resistance value of the valve piece R1 of the counter is small the pressure drop at 10 kA is 1 1 kV the flow capacity is large 1200 A square wave and the minimum operating current is 100 A 8 20s impulse current III Technical Parameter 1 Output voltage DC3000V 5 2 Interval time 30s 3 Power supply AC200V 10 50Hz 2 4 Shock current 100A 8 20μs 5 Dimension 380 250 180mm 6 Weight 3kg IV Inspe...

Страница 6: ...the recorder is normal the instrument is good otherwise it should be dismantled and repaired For example a power bureau has used this method to detect 27 counting devices of which 3 are not moving and the internal components are found damped and damaged after disintegration The Regulations stipulate that continuous testing should be carried out 3 to 5 times each time should be normal and each time...

Страница 7: ...f the counter 6 Turn off the power immediately after the inspection and remove the connection only when the output voltage returns to zero 7 If the output voltage does not decline after pressing the check key the power should be turned off After the voltage indicator returns to zero check whether there is a break point in the loop or whether the discharge counter is not suitable for the model spec...