7
5. List of User Parameters
Level 1
Menu
Level 2
Menu
Initial
Value
Function
Connection
Parameter
Preset
Connection
Status
Host /
Slave
Multiple machines are connected as "host" or "slave"
for operation, and the host controls the start, stop,
loading and unloading of the slave according to air
pressure.
Rotation Time
0099
hrs
When connected for operation, set the working of the
machines within the allowable pressure range, and the
machines rotate in turn after the preset time.
Number of
Connected
Machines
0000
When connected for operation, set the number of air
compressors in the network.
Connection
Lower
Pressure
Limit
00.00
MPa
When connected for operation, find a machine in the
network to load or start when the host pressure is lower
than this preset pressure.
Connection
Upper
Pressure
Limit
00.00
MPa
When connected for operation, find a machine in the
network to unload or stop when the host pressure is
higher than this preset pressure.
Connection
Delay
0050 s
When connected for operation, set the wait time for
continuously sending control command twice by the
host.
Language
Selection
Chinese
Chines
e
User
Password
****
****
User or manufacturer can modify the user password
after permissions are verified.