Advanced Cooling Controller
User Manual
5 FAQ
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
52
Required cooling capacity: indicates the total cooling/heating requirements of the group and is used
as a reference for enabling the cooling/heating mode by the master device. If the cascade function is
enabled, the capacity is used as a reference for determining whether to start a standby unit.
Required humidity: indicates the total dehumidification and humidification requirements of the
group and is used as a reference for enabling the dehumidification and humidification mode by the
master device.
----End
5.10 Which Parameters Are Restored to Default Values
After Default Settings Are Operated
After choosing
Settings
>
Restore Defaults
>
Yes
, the following parameters are displayed:
All parameters displayed on
Settings
>
System Settings
.
All parameters displayed on
Settings
>
Alarm Settings
.
All parameters displayed on
Settings
>
Comm Settings
.
Date format and time zone settings displayed on
Settings
>
User Settings
.
All parameters displayed on
Maint
>
Sensor Adjust
.
To prevent loss of important data, record all parameter values before restoring default settings.
After restoring default settings, change the parameter values to the recorded values.
After default settings are restored, all communication addresses are changed to 1 and the communication
between all devices and the EMS is disconnected. The communication addresses must be reset to
recover the communication.
5.11 How to Change the SSH Access Password
Context