UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
61
Non-Secured Installation
Step 1
Lower the four leveling feet at the bottom of the cabinet until all the four castors at the bottom
are lifted from the ground and the leveling feet bear the full cabinet weight, as shown
Figure 3-15
Castors adjustment
Step 2
Check whether the bottom of the cabinet is horizontal by using a level. If the cabinet is not
level, adjust the leveling feet.
----End
3.2.2 Installing Batteries
Context
Before installing batteries, read through the battery safety precautions, obtain the delivered
battery installation guide, and install batteries as instructed.
Place the batteries in a correct way to prevent vibrations and shocks.
Install the batteries from the lower layer to the upper layer to prevent falling over due to
imbalance.
Procedure
Step 1
Install a battery rack and batteries.
For details, see the battery installation guide delivered along with batteries.
----End