The battery cable specifications are selected based on 40 batteries by default and
compatible with application scenarios with 30–44 batteries.
When the mains input and bypass input share a power source, configure both types of
input power cables as mains input power cables. The cables listed in
only when the following requirements are met:
−
Routing mode: Routing the cables over the cable ladder or bracket in a single layer
(IEC60364-5-52 middle E). The distances between cables must be greater than
twice the cable diameter.
−
The ambient temperature is 30°C.
−
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
−
90°C copper flexible cable.
−
The length of the AC power cables of a UPS is no longer than 30 m and DC power
cables no longer than 50 m.
When you connect power cables, comply with the tightening torque listed in
ensure secure connections and prevent safety risks.
Table 3-4
Power cable connector requirements
Connect
or
Connection
Mode
Bolt Type Bolt Hole
Diameter
Bolt Length Torque
Mains
input
connector
Crimped DT
terminals
M16
18 mm
50 mm
120 N·m
Bypass
input
connector
Crimped DT
terminals
M16
18 mm
50 mm
120 N·m
Battery
input
connector
Crimped DT
terminals
M16
18 mm
50 mm
120 N·m
Output
connector
Crimped DT
terminals
M16
18 mm
50 mm
120 N·m
Groundin
g
connector
Crimped DT
terminals
M12
/
35 mm
47 N·m
Table 3-5
Recommended input front-end and output back-end circuit breakers
UPS Capacity
Component
Specifications
a
350 kVA
Mains input circuit breaker
800 A/3P