A Alarm List
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
174
Alarm ID
(Alarm ID-
Cause ID)
Alarm Name
Severity
Cause
Solution
0565-1
Load impact
transfer-to-
bypass
Minor
A large-power RCD
load is instantly
connected, or the output
load short-circuits.
The inverter bridge
short-circuits.
1.
Check the load.
2.
If the load is normal,
replace the power unit.
0566-1
Output
overload
Minor
The load is excessive.
Derating reduces the
rated system power.
The unit is damaged.
1.
Check that there is no
overload.
2.
Check that the unit power
is not derated due to a fan
fault.
3.
If the alarm persists,
replace the power unit.
0570-4
BPM unit
abnormal
Critical
The bypass fan is not
functioning properly, or
the air channel is
blocked.
The ambient
temperature exceeds the
upper threshold.
The load is excessive.
1.
Check the bypass fan and
air channel. If the fan is
faulty, replace it.
2.
Check that the ambient
temperature has not
exceeded 40°C.
3.
Check that there is no
overload.
0583-1
Inter-rack par.
cable abnormal
Critical
The inter-rack parallel
system CAN bus is
disconnected or short-
circuited.
Only one rack works in
a parallel system.
An ECM is faulty.
1.
Check the inter-rack
parallel system CAN bus.
2.
Rectify the disconnection
or short-circuit fault.
3.
Replace the ECM.
0583-4
The inter-rack industrial-
frequency synchronization
cable is broken.
Replace the inter-rack
parallel cable.
0583-5
The inter-rack carrier
synchronization cable is
broken.
0583-6
The intra-rack INVBYP
cable is broken.
The parallel CAN bus is
broken.
0584-2
Inter-rack par.
cable alarm
Minor
The inter-rack parallel
cable is faulty.
Replace the parallel cable.
0584-4
The inter-rack industrial
frequency synchronization
cable is broken.