UPS5000-A-500 kVA
User Manual (e-shelter)
5 Operations
Issue 02 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
146
Figure 5-10
BCB connection setting
----End
5.2 Shutting Down and Powering Off the UPS
Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is not normal, the UPS supplies no power. Before shutting down the UPS, ensure
that all loads have shut down.
Procedure
Step 1
Shut down the inverter.
On the LCD
On the main screen, tap
Common Functions
. Tap
Inv. OFF
.
To shut down the inverter on the
Maintenance
screen, tap
System Info
>
Maintenance
.
On the WebUI
On the homepage, choose
Monitoring
>
Control
, and click
Inv. OFF
. In the displayed
dialog box, click
OK
to shut down the inverter.
After the inverter shuts down, the UPS works in bypass mode if the bypass is normal, as
shown in
; the UPS supplies no power and the loads power off if the bypass is