background image

C14/C19 

C13/C20 

UPS 

10 A max. 

Installing Cables 

Connecting the UPS 
 

4.1 

1. Connect a power cable from UPS input to UPS input outlet on the unit. Use another power 

cable to connect UPS output to UPS output outlet on the unit.  

2. Refer to cable connection of UPS2000-G-2KRTL when connecting UPS2000-G-

1KRTL/1KRTS/2KRTS. Refer to cable connection of UPS2000-G-3KRTL when connecting 
UPS2000-G-3KRTS.  

3. 3 kVA UPS output form factor (terminal or C20) varies with different actual models. 

NOTE

UPS2000-G-2KRTL 

UPS2000-G-3KRTL 

Installing the Unit 

Rack-mounting 
 

Scenario 

Front 

Rear 

NOTICE

When installing, ensure that the 
PDU rear panel is aligned with 
the UPS rear panel. 

C19/C20 

C20/C19 

UPS 

16 A/16 A 

16 A/16 A 

C19/C20 

Terminal/C19 

UPS 

Содержание UPS2000-MBS-16A

Страница 1: ...talling the unit ensure that the sum of the leakage currents of the unit and the devices it powers does not exceed 3 5 mA NOTICE 1 Slave outlets 2 Master outlets 3 Power indicator 4 Slave on indicator 5 Bypass switch 6 Outlet for UPS output 7 Outlet for UPS input 8 AC input 9 Circuit breaker 10 Master slave function switch Issue 01 Date 2016 03 25 UPS2000 MBS 16A PDU Maintenance Bypass Switch Modu...

Страница 2: ... G 2KRTL when connecting UPS2000 G 1KRTL 1KRTS 2KRTS Refer to cable connection of UPS2000 G 3KRTL when connecting UPS2000 G 3KRTS 3 3 kVA UPS output form factor terminal or C20 varies with different actual models NOTE UPS2000 G 2KRTL UPS2000 G 3KRTL 2 Installing the Unit 3 Rack mounting Scenario Front Rear NOTICE When installing ensure that the PDU rear panel is aligned with the UPS rear panel C19...

Страница 3: ...he mains is normal The Power indicator will turn off when there is a power failure 1 The master slave function is disabled by default Ensure that the master slave function switch is on the disable status before operation 2 Only when the master slave function is enabled loads connected to slave outlets will be shut down after load is detected lower than 10 W in master outlet 3 Master slave function...

Страница 4: ...this time all connected devices are powered by the mains directly Turn off the UPS and disconnect two cables connected to the UPS Then you can maintain the UPS After maintaining the UPS ensure that the UPS operates properly Reconnect the UPS to the unit by following the installation section Verify that the Power indicator is on Turn on the UPS then transfer the rotary bypass switch from MBS to UPS...

Отзывы: