UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
36
Alarm
ID
Alarm
Cause
ID
Alarm
Name
Alarm
Severity
Alarm
Clear
Mode
Trigger
Condition
Impact on
the System
Repair Proposal
load or replace the
UPS with a UPS
with a larger
capacity.
66
3
Output
overloa
d
Critical
This alarm
must be
manually
cleared.
In
battery
mode,
this
alarm is
generat
ed
when
the load
exceeds
the
rated
load.
In
normal
mode,
when
the
bypass
input is
normal,
this
alarm is
generat
ed
when
the UPS
transfer
s to
normal
mode
three
times
within
20
minutes
after the
UPS
transfer
s from
normal
mode to
bypass
mode.
In
normal
For battery
mode, the
UPS
transfers to
no output
mode.
If the UPS
transfers
from
normal
mode to
bypass
mode three
times
within 20
minutes,
the UPS is
locked in
bypass
mode.
For normal
mode, the
UPS
transfers to
no output
mode.
Possible cause: The
load exceeds the
rated loading
capacity of the
inverter.
Measure: Lower the
load or replace the
UPS with a UPS
with a larger
capacity.