UPS2000-G-(1 kVA-3 kVA)
User Manual (2016, Russia)
4 Setting Control Panel
Issue 02 (2016-07-28)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
28
Alarm
ID
Alarm
Cause
ID
Alarm
Name
Alarm
Severity
Alarm
Clear
Mode
Trigger
Condition
Impact on
the System
Repair Proposal
the bypass input
recovers.
2
Bypass
freque
ncy
abnor
mal
Minor
This alarm
is
automatic
ally
cleared.
The bypass
frequency
is outside
the bypass
frequency
range.
The UPS
remains in the
current state.
If the UPS
works in
bypass mode,
it transfers to
standby mode
and has no
output.
Possible cause: The
bypass input
frequency is
abnormal.
Measure: Check
whether the bypass
input frequency
exceeds the
configured range. If
yes, change the
range or wait until
the bypass input
recovers.
14
1
Startup
timeou
t
Critical
This alarm
must be
manually
cleared.
The
inverter
output
voltage is
not within
±2 V of the
rated
output.
If this alarm is
generated
during the
running of the
UPS, the UPS
transfers to
bypass mode.
Possible cause:
The bypass
loading capacity
exceeds the rated
load of the
inverter.
Measure: Reduce
the output load,
manually clear
the alarm, and
restart the UPS.
Possible cause:
An internal fault
has occurred.
Measure: Contact
the dealer or
Huawei technical
support.
Minor
This alarm
is
automatic
ally
cleared.
Discharge
ends for
the UPS in
battery
mode, or
the battery
voltage is
lower than
the
minimum
startup
voltage
(11.28 V)
for the
UPS in
The UPS fails
to start.
Possible cause: The
battery voltage is
low or the batteries
are damaged after
EOD.
Measure: Wait for
the batteries to
recover or contact
the battery supplier
to replace the
batteries.