TP48200A-D17B3
Troubleshooting Guide
4 Troubleshooting
Issue 03 (2013-05-06)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
28
Solution
Step 1
Check that the PSU is installed properly.
Step 2
Check whether the communication cable between the PSU and the signal transfer board is
properly connected. If the cable is properly connected, restart the PSU.
Step 3
If the alarm persists, replace the PSU.
Step 4
If the alarm persists after the PSU is replaced, replace the signal transfer board.
----End
4.3.17 D.G. Fault
Possible Causes
The D.G. signal cable is faulty.
The PMU is not configured properly.
The D.G. is faulty.
Solution
Step 1
Check that the signal cable is properly connected to the D.G.
Step 2
Check that the start permission of the D.G. in the PMU is set to NO and that the diesel
generator is started manually. The alarm is cleared after you shut down the D.G.
Step 3
Check the D.G. by referring to the diesel generator user guide.
----End
4.3.18 Load Fuse Disconnection
Possible Causes
The load circuit breaker is set to OFF.
Solution
Step 1
Check that the load circuit breaker is set to ON.
Step 2
If the circuit breaker is automatically set to OFF after you set it to ON, check whether the load
branch is overloaded or short-circuited. Rectify the load route fault.