TP48200A-D17B3
Troubleshooting Guide
4 Troubleshooting
Issue 03 (2013-05-06)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
24
4.3.6 Load Shutdown
Possible Causes
The load circuit breaker is set to OFF.
The contactor is faulty.
The PMU load shutdown voltage is excessively high.
Output undervoltage occurs because the load power is greater than the configured PSU
power.
Solution
Step 1
Check that the load detection cable is properly connected.
Step 2
Check the position of the handle on the circuit breaker and ensure that the circuit breaker is
turned on.
Step 3
Check the contactor, for example, whether it can be opened and closed. Replace the faulty
contactor.
Step 4
Check that the PMU load shutdown voltage is set properly.
Step 5
Check whether the load power is higher than the configured PSU power. If the load power is
higher than the configured PSU power, add a PSU and set the number of PMUs. Ensure that
the load power is within the supported range.
----End
4.3.7 Battery Shutdown
Possible Causes
PMU battery parameters are not set properly.
The contactor is faulty.
Solution
Step 1
Check that the mains supply is off and that the voltage of storage batteries drops below the
specified battery shutdown voltage.
Step 2
Check that battery shutdown is allowed.
Step 3
Check battery cables or connectors. Replace faulty cables or connectors.
Step 4
Check the contactor, for example, whether it can be opened and closed. Replace the faulty
contactor.
----End
4.3.8 Battery Loop Failure
Possible Causes
The battery route is faulty.