TP48200A-D14A1 Telecom Power
User Manual
3 Component Description
Issue 04 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
24
Table 3-4
Power distribution specifications
Item
Specifications
AC power
distribution
Main AC input
One 100 A two-pole MCB;
DC power
distribution
Load shutdown
BLVD: 10 A MCB x 2; 16 A MCB x 3
LLVD: 20 A MCB x 8; 63 A MCB x 1
Battery branch
100 A MCB x 1
3.5 Monitoring Unit
Appearance
The monitoring unit is 1 U (44.45 mm [1.75 in.]) high, and can be installed in a 19-inch rack.
Figure 3-9 shows the monitoring unit.
Figure 3-9
Monitoring unit
PMU02C1
The PMU provides a RUN LED (green), an ALM LED (red), an embedded buzzer, and a
(LCD) that displays the operating parameters, operating status, alarm
status, configured parameters, and controlling parameters of the DC power, AC power, PSUs
and storage batteries. These parameters are collected by the PMU. Detail information refer to
6.1.1 PMU02C1.
UIM02A
The UIM02A panel provides sensor detection ports, Boolean value input ports, dry contact
outputs. Please refer to 6.1.2 UIM02A6.1.2 UIM02A.
Network Diagrams
Figure 3-10 shows the network diagram.