![Huawei TP48200A-D14A1 Telecom Power Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/huawei/tp48200a-d14a1-telecom-power/tp48200a-d14a1-telecom-power_user-manual_169594026.webp)
TP48200A-D14A1 Telecom Power
User Manual
3 Component Description
Issue 04 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
20
3.2 Temperature Control System
3.2.1 Overview
The temperature control system of the TP48200A-D14A1 is composed of a direct-cooling
unit. The temperature control system accelerates the air ventilation and reduces the
temperature inside the cabinet by using fans and other ventilation devices.
Figure 3-2
Fan speed line chart
Table 3-1
Technical specifications of the temperature control system
Item
Specifications
Operating
temperature
-40°C to +50°C (include 1120W/M
2
sun radiation)
Cooling capacity
Rated power:1500W; Maximum power: 1700 W
Acoustic noise
ETS 300 753 Class 4.1 (rural environment)
3.2.2 Direct-Cooling Unit
The direct-cooling unit consists of an air-exhaust device, an air-intake device, an air filter, and
a fan assembly. The direct-cooling unit extends the area for exchanging air inside and outside
the cabinet, speeds up air circulation, and reduces the operating temperature in the cabinet.
Air-exhaust device
The air-exhaust device is mounted in the upper part on the interior of the cabinet door, as
shown in Figure 3-3.
Air-intake device
The air-intake device as shown in Figure 3-3.