TP48200A-HT19C3 and TP48200A-HT19C4 Telecom
Power
User Manual
3 Components
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
34
Figure 3-14
TCUA
(1) Power input port
(2) External circulation fan
port 1
(3) External circulation fan
port 2
(4) Switch port (reserved)
(5) Door status sensor port
(6) Electronic label port
(reserved)
(7) Indicator
(8) Communications port 1
(9) Communications port 2
(10) Temperature signal
port 1
(11) TEC air conditioner
port
(12) Internal circulation fan
port 1
(13) Internal circulation fan
port 2
(14) Temperature signal port
2
TEC Working Principle
The TEC cools and heats air through internal and external circulation. Table 3-11 describes
how the TEC works. Figure 3-15 shows the TEC airflow directions.
Table 3-11
TEC working principles
Function
Working Principle
Cooling
The TCUA control box controls the refrigeration chip in the TEC module to cool the
internal circulating air. The internal circulation fan draws the air inside the battery
compartment into the internal circulation heat sink. The internal circulation heat sink
cools the air and then returns the cooled air to the battery compartment through the air
exhaust vents. Meantime, the external circulation fan draws natural air into the external
circulation heat sink to accelerate the airflow. The air absorbs the heat from the external