Figure C-1 Setting export limitation parameters
Table C-1 Control mode
Parameter
Description
Unlimited
N/A
-
If this parameter is set to Unlimited,
the inverter output power is not
limited. The inverter can export its
rated power to the power grid.
Grid
connected
with zero
power
Closed-loop
controller
● SDongle/
SmartLogger
● Inverter
● Set this parameter to SDongle/
SmartLogger when the
SmartLogger1000A is connected.
● If multiple inverters are cascaded,
set this parameter to SDongle/
SmartLogger.
● If there is only one inverter, set
this parameter to Inverter.
Limitation mode
● Total power
● Single-phase power
● If this parameter is set to Total
power, it indicates that no
backfeeding occurs for the three
phases.
● If this parameter is set to Single-
phase power, it indicates that no
backfeeding occurs for the phase
with the maximum power.
Power lowering
adjustment
period
-
Specifies the shortest interval for a
single anti-backfeeding adjustment.
SUN2000-(3KTL-10KTL)-M0
User Manual
C Setting Export Limitation Parameters
Issue 06 (2020-10-23)
Copyright © Huawei Technologies Co., Ltd.
92