5 Electrical Connections
Issue 04 (2016-06-20)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
43
It is recommended that the ground cable be connected to a nearby ground position. For a
system with multiple inverters connected in parallel, connect the ground points of all
inverters to ensure equipotential connections.
Procedure
Step 1
Strip an appropriate length of the insulation layer of the ground cable using a wire stripper, as
shown in
Figure 5-1
.
Figure 5-1
Stripped length
Step 2
Insert the exposed core wires into the crimping area of the OT terminal and crimp them using
hydraulic pliers, as shown in
Figure 5-2
.
Figure 5-2
Crimping a cable
The crimping must result in full containment of the cable conductors and complete contact between the
cable conductors and the terminal.
Step 3
Remove the ground screw from the ground point.
Step 4
Secure the ground cable using the ground screw and tighten the screw to a torque of 5 N·m