SUN2000-(175KTL-H0, 185KTL-INH0, 185KTL-H1)
User Manual
8 Maintenance
Issue 02 (2019-06-05)
Copyright © Huawei Technologies Co., Ltd.
77
Alarm
ID
Alarm
Name
Alarm
Severit
y
Cause
Troubleshooting Suggestions
2038
Unstable
Grid
Frequenc
y
Major
Power grid exception: The actual grid
frequency change rate does not comply
with the local power grid standard.
1.
If the alarm occurs
occasionally, the power grid
may be abnormal temporarily.
The inverter automatically
recovers after detecting that
the power grid becomes
normal.
2.
If the alarm occurs frequently,
check whether the power grid
frequency is within the
acceptable range. If not,
contact the local power
operator.
2039
Output
Overcurr
ent
Major
The power grid voltage drops
dramatically or the power grid is
short-circuited. As a result, the inverter
transient output current exceeds the
upper threshold and therefore the
inverter protection is triggered.
1.
The inverter detects its
external working conditions in
real time. After the fault is
rectified, the inverter
automatically recovers.
2.
If the alarm occurs frequently
and affects the energy yield of
the power plant, check whether
the output is short-circuited. If
the fault cannot be rectified,
contact your dealer or Huawei
technical support.
2040
Output
DC
Compon
ent
Overhigh
Major
The DC component of the inverter
output current exceeds the specified
upper threshold.
1.
If the exception is caused by
an external fault, the inverter
automatically recovers after
the fault is rectified.
2.
If this alarm occurs frequently
and affects the energy yield of
the PV plant, contact your
dealer or Huawei technical
support.
2051
Abnorma
l
Residual
Current
Major
The insulation impedance of the input
side to PE decreases when the inverter
is operating.
1.
If the alarm occurs
occasionally, the external
circuit may be abnormal
temporarily. The inverter
automatically recovers after
the fault is rectified.
2.
If the alarm occurs frequently
or persists, check whether the
impedance between the PV
string and the ground is too
low.