HUAWEI TECHNOLOGIES CO., LTD. 

SUN2000 (8KTL-28KTL) 

Quick Installation Guide 

Issue: 13 
Part Number: 31505445 
Date: 2015-08-03 

Содержание SUN2000-10KTL

Страница 1: ...0 HUAWEI TECHNOLOGIES CO LTD SUN2000 8KTL 28KTL Quick Installation Guide Issue 13 Part Number 31505445 Date 2015 08 03 ...

Страница 2: ...the user manual log in to http support huawei com carrier and browse or search for SUN2000 on the Product Support page 2 Use insulated tools Inverter Model Weight SUN2000 8KTL 10KTL 12KTL 40 kg SUN2000 15KTL 17KTL 20KTL 23KTL 28KTL 48 kg Determine the installation position Unit mm Install the SUN2000 in a position where the liquid crystal display LCD is easy to view and operate Vertical Backward F...

Страница 3: ...ails about wall mounting the device see the SUN2000 8KTL 28KTL User Manual 1 Determine the hole positions on the support based on rear panel dimensions 2 Drill holes 3 Secure the rear panel 4 Mount the inverter on the rear panel 5 Tighten hexagon bolts 6 Optional Install an anti theft lock M10 3 PCS 30 N m Unit mm NOTE ...

Страница 4: ...UN2000 15KTL 17KTL 20KTL 23KTL 28KTL 6 0 mm2 10 AWG 10 0 mm2 8 AWG The table lists only the recommended cable specifications For more information about cable specifications see the SUN2000 8KTL 28KTL User Manual 2 Electrical Connection OT 6mm2 M6 PE terminal 1 Install a ground cable 1 It is recommended that the ground cable be connected to a nearby ground position 2 To enhance the corrosion resist...

Страница 5: ... is securely connected Otherwise the connector may be damaged after the inverter has been running for a long time 3 Install DC input power cables Optional DC input terminals Number of Inputs 8KTL 12KTL 15KTL 28KTL 1 Connects to any one route Connects to any one route 2 Connects to routes 1 and 3 Connects to routes 1 and 3 3 Connects to routes 1 2 and 3 Connects to routes 1 3 and 5 4 Connects to ro...

Страница 6: ...ver is fastened 1 Pull back the DC input power cables to check whether the cables would be disconnected 2 If DC input power cables are reversely connected and the DC switch is ON do not turn off the DC switch immediately Otherwise the equipment may be damaged You can disconnect the DC input power cable on the PV string side or wait until the PV string voltage reduces to a value within the safety r...

Страница 7: ...at all circuit breakers are switched to OFF Passed Failed 3 Check that the ground cable is securely connected and no short circuit occurs Passed Failed 4 Check that AC output power cables are connected correctly and securely the N wire is connected to hole 4 and L1 L2 L3 can be connected to any hole of 1 2 3 for details see 2 2 Install AC output power cables with no short circuit Passed Failed 5 C...

Страница 8: ...wer grid choose CHINA MV480 China low voltage power grid choose NB T 32004 For other cases see the Appendix Main Menu Settings Isolation Ad vanced User Input Grounded With TF When the PV is grounded an isolation transformer should be connected Set Isolation to Input Grounded With TF When the PV is not grounded set Isolation to Input Ungrounded Without TF or Input Ungrounded With TF Input Ungrounde...

Страница 9: ...cotland Scotland 240 V power grid I 16 A 34 Japan 50Hz Japan power grid 50 Hz 12 CEI0 21 Italian low voltage power grid 35 Japan 60Hz Japan power grid 60 Hz 13 CEI0 16 Italian medium voltage power grid 36 EN50438 TR MV480 Turkey medium voltage power grid 14 IEC61727 IEC low voltage power grid 37 EN50438 TR Turkey low voltage power grid 15 VDE 0126 1 1 GR A Mainland of Greece low voltage power grid...

Страница 10: ...9 HUAWEI TECHNOLOGIES CO LTD Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China www huawei com ...