6
Without an air deflector
With an air deflector
Front view
Side view
Front view
Side view
• Reserve 10 U space between the devices or add a 3 U air deflector to redirect air flows to
minimize the mutual heat dissipation impacts on the devices.
• Reserve at least 2 U space for air flow-in when you route fibers or install other passive devices.
You are advised to reserve more than 4 U space to facilitate subsequent air inlet or dust filter
cleaning.
5.2 When the Cabinet Accommodates One MA5800-X15 Subrack and
Another Device
5 Space Requirements on Third-Party Cabinets
3U
10U
4U
2U
4U
Air deflector (3 U)