RMS-SNMP01A SNMP Card
User Manual
4 Managing the UPS on the WebUI
Issue 08 (2020-01-09)
Copyright © Huawei Technologies Co., Ltd.
33
CIM No
: The No. of CIM connected to the battery strings. The No. cannot be greater
than the
Number of CIMs
set on the
Config
>
Comm. Config page
. One
CIM No.
can
only be set for one UPS.
BIM Start No
: The No. of the first BIM connected to each battery string.
BIM End No
: The No. of the last BIM connected to each battery string. The BIM End
No. cannot be smaller than the
BIM Start No.
, and cannot be greater than the
Number
of BIMs
set on the
Config
>
Comm. Config page
.
Figure 4-13
Parameter settings (battery string settings)
The battery string settings are available only when the CIM is configured. If you need to configure
battery strings, set the CIM parameters first by referring to the CIM settings section in
. After the value of
Number of battery strings
or
Number of batteries in a battery
string
is modified and submitted successfully, the battery string information will be cleared.
Number of battery strings
and
Number of batteries in a battery string
refer to information about
the battery strings connected to the UPS. The parameters are not sent to the CIMs. The SNMP card
associates the battery string information with UPSs. The settings of these two parameters are
different from the settings in
Config
>
Comm. Config
>
CIM Information Settings
.
A UPS system can connect to a maximum of four CIMs. Different UPSs cannot connect to the same
CIM.
For details about the connection settings for the UPS2000 and CIM, see
4.4.4 Control Page
In the UPS information area, choose
Control
>
System Commands and Tests
, and you can
start or shut down the UPS. For UPS2000-G you can also perform battery maintenance. The
buttons in red are available, and those in gray are unavailable, as shown in